Optical-Thermal Detector
OH-13001
•Addressable conventional technology
•Combination of optical and thermal characteristics of fire
•Individual detector addressing by means of optional address module
•Optional connection of remote indicator
•Sealed electronics
Description
The
Intelligent evaluation algorithms compensate for the contamination of the optical measurement system, thus keeping the response sensitivity of the detector constant for a long time. In this way, false alarms can
be avoided to a great extent. If the contamination can not be compensated any further, or if a fault occurs in the measurement system, this is indicated by a yellow fl ashing of the multicoloured status LED.
Addressable conventional technology is used for alarm transmission to the fi re detection control panel. By means of the optional Address Module
The detector can be attached to various bases and it can be protected against theft.
Specifications
Operating voltage | Supply through the detector line voltage |
Current consumption | typ. 65µA (quiescent) |
Ambient temperature | - 40°C to +70°C (no condensation or icing) |
Relative humidity | 0 – 98% (no condensation) |
Dimensions ø × H | 100 × 42 (mm) |
Colour | white |
Weight | 80g |
Approval | VdS G204040 |
Order number | 241061 |
Order name |
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • | |
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED |
|