Remote Tableau Drive Unit

PTU288-1 and Accessories

Optically and acoustically signals the events of a fire detection or extinguishing control panel

Actuation of up to 144 LED pairs, single LEDs or relays

Single or summary indication parameterisable

Connection to the INFO bus

Easy parameterisation by means of PC software PARSOFT

Description

The Remote Tableau Drive Unit PTU288-1 allows to op- tically signal events of a Fire Detection Control Panel Series BC216 or BC016, or of an Extinguishing Control Panel Series LC216, on an optional synoptic remote tableau. In addition, a built-in buzzer signals the alarm or fault condition of the control panel.

Up to 3 LED Display Fields LAB48 or LED Connection Modules LAM48-1 can be connected to the remote tab- leau drive unit in any combination.

In accordance to the parameterisation, the LEDs can be used to display the conditions of detectors, detector zo- nes, actuations, actuation elements, alarming devices, transmitting devices, extinguishing systems or fl ooding zones as well as the most important system conditions of the fi re detection control panel (e.g., summary alarm, fault condition or disablement condition). If needed, it is also possible to combine several events into a summary display.

Furthermore, the PTU288 has 5 freely parameterisable control inputs.

The remote tableau drive unit is connected to the fi re detection control panel via the INFO bus. Auxiliary mo- dules are not needed for connection to Control Panels Series BC216. A Serial Interface Module SIM016-3 is necessary for connecting the PTU288 to a Fire Detec- tion Control Panel Series BC016.

The PC software PARSOFT is used to parameterise the remote tableau drive unit via the USB interface.

The componentry is prepared for direct installation into the LED Display Tableau LAT288-1 or LAT288-1CE. The componentry can also be mounted in any housing in the LST standard grid, using the supplied mounting parts.

Specifications

Operating voltage

15 – 31VDC

Current consumption at 24V

typ. 15mA (without LED modules)

Ambient temperature

-20°C to +60°C

Dimensions L × W × H

150 × 75 × 20 (mm)

Weight

76g

Order number

252012

Order name

Remote Tableau Drive Unit PTU288-1