At disablement of the primary transmitting device or the primary alarming device, the correspond-
ing yellow disablement-LED-displays are illuminated.
The menu jumps automatically to the menu point [Disablements] 30 seconds after any button was
pressed last, if no event of higher priority is currently on the control panel.
The first line of the LC-display shows the first disablement. The second and third line display addi-
tional text (e.g., a zone-, or an element-specific text) for the disablement displayed in the first line.
The fourth line is reserved for displaying fire alarms. The disablements are numbered in order of
their execution.
1.DISABLEM. 0001/029
<zone text1>
<element text>
Figure 21: Display in the condition of disablement
Element Nr. 29 of the detector zone Nr. 1 is displayed as the first executed disablement. The second
and third line display information on this disablement. Has no element text been programmed, the
second zone text (if available) is displayed. The fourth line is reserved for fire alarm messages.
Additional information (e.g., date and time of the disablement, the number of current disablements,
hints for operating the menu, hints for authorization) can be displayed by using the 'Info'-button. You
can scroll through all current disablements by using the '↑↓'-buttons.
The following disablements are displayed on the LC-display of the control panel:
Condition Displaying (1st line)
Disablement of a detector zone (e.g., Nr. 4) for fire alarms 1.DISABLEM. 0004
Disablement of an element (e.g., Nr. 29) of a detector zone (e.g., Nr. 4)
for fire alarms 1.DISABLEM. 0004/029
Disablement of a detector zone (e.g., Nr. 3) for technical messages 1.TECH.DIS 0003
Disablement of an element (e.g., Nr. 5) of a detector zone (e.g., Nr. 3) for
technical messages 1.TECH.DIS 0003/005
Disablement of a detector zone (e.g., Nr. 5) for fault messages 1.FLT.DIS 0005
Disablement of an element (e.g., Nr. 14) of a detector zone (e.g., Nr. 5)
for fault messages 1.FLT.DIS 0005/014
Disablement of an actuation zone (e.g., Nr. 2) 1.ACTU.DIS 0002
Disablement of an element (e.g., Nr. 18) of an actuation zone (e.g., Nr. 2) 1.ACTU.DIS 0002/018
Disablement of an actuation zone (e.g., Nr. 2), automatically in authoriza-
tion level 2 or 3 1.ACTU.DIS* 0002
Disablement of a transmitting device (e.g., Nr. 1) 1.TR-DEV.DIS 01
Disablement of a transmitting device (e.g., Nr. 1), automatically in
authorization level 2 or 3 1.TR-DEV.DIS* 01
Disablement of an alarming device (e.g., Nr. 1) 1.AL-DEV.DIS 01
Table 5: Messages of the disablement condition
HB216AE.SAM / 0130 / AN9161202
ZN5002/73/62
62 Chapter 5 Operating conditions of fire detection control panels Series BC216 User Manual Series BC216 / Part A