7 Event memory - entries
You can browse in the event memory by the use of the '↑↓'-buttons. The first three lines of the LC-
display show the event text as well as the free programmable text information on the event, and provide
additional information on events on the control panel. By pressing the 'Info'-button, additional texts
(e.g., the reason for a given fault) appear, as well as the date and time of the occurrence or of the termi-
nation of the event.
Event Event text Text 2nd line Text 3rd line Additional text
(info-button)
Fire detector zones/elements
Activation ALARM 0001/001 zone text 1 zo. text 2 / element text
Activation termination ALARM.T 0001/001 zone text 1 zo. text 2 / element text
Disablement DISABLEM. 0001/001 zone text 1 zo. text 2 / element text
Enablement ENABLEMENT 0001/001 zone text 1 zo. text 2 / element text
Fault FAULT 0001/001 zone text 1 zo. text 2 / element text fault cause
Fault termination FAULT.T 0001/001 zone text 1 zo. text 2 / element text fault cause
Pre-alarm PRE-AL 0001/001 zone text 1 zo. text 2 / element text
Pre-alarm termination PRE-AL.T 0001/001 zone text 1 zo. text 2 / element text
Test activation TEST-AL 0001/001 zone text 1 zo. text 2 / element text
Test activation termination TEST-AL.T 0001/001 zone text 1 zo. text 2 / element text
Test condition off TEST COND.T 0001/001 zone text 1 zo. text 2 / element text
Test condition on TEST COND 0001/001 zone text 1 zo. text 2 / element text
Technical detector zones/elements
Activation TECH.MSG 0001/001 zone text 1 zo. text 2 / element text
Activation termination TECH.MSG.T 0001/001 zone text 1 zo. text 2 / element text
Disablement TECH.DIS 0001/001 zone text 1 zo. text 2 / element text
Enablement TECH.ENA 0001/001 zone text 1 zo. text 2 / element text
Fault TECH.FLT 0001/001 zone text 1 zo. text 2 / element text fault cause
Fault termination TECH.FLT.T 0001/001 zone text 1 zo. text 2 / element text fault cause
Test activation TECH.T-AL 0001/001 zone text 1 zo. text 2 / element text
Test activation termination TECH.T-AL.T 0001/001 zone text 1 zo. text 2 / element text
Test condition off TECH.TEST.T 0001/001 zone text 1 zo. text 2 / element text
Test condition on TECH.TEST 0001/001 zone text 1 zo. text 2 / element text
Fault detector zones/elements
Activation FLT-ALARM 0001/001 zone text 1 zo. text 2 / element text
Activation termination FLT-ALARM.T 0001/001 zone text 1 zo. text 2 / element text
Disablement FLT.DIS 0001/001 zone text 1 zo. text 2 / element text
Enablement FLT.ENA 0001/001 zone text 1 zo. text 2 / element text
Fault FLT.FLT 0001/001 zone text 1 zo. text 2 / element text fault cause
Fault termination FLT.FLT.T 0001/001 zone text 1 zo. text 2 / element text fault cause
Test activation FLT.T-AL 0001/001 zone text 1 zo. text 2 / element text
Test activation termination FLT.T-AL.T 0001/001 zone text 1 zo. text 2 / element text
HB216AE.SAM / 0130 / AN9161202
ZN5002/73/68
68 Chapter 7 • Event memory - entries User Manual Series BC216 / Part A