RESET/SILENCE SWITCH

The switch on the front of the CM-S1 labeled “TEST/RESET,” performs three functions.

1.) A short press of switch, less than 5 seconds long, will place the unit into self test mode with no alarm relay activation. The status light will turn red for 5 seconds and then it will alternate slowly between green and amber while the self-test executes. The controlling software simulates a 3000 ppm CO environment and causes the unit to alarm after approximately one minute has elapsed. When this happens, the status light turns red and the buzzer will sound two complete alarm cycles. The unit will then return to normal operation.

2.) A long press of switch, about 6 seconds long, will place the unit into self-test mode with alarm relay activation. Pressing and holding the switch will cause the status light to turn red for 5 seconds and then switch to solid amber. The alarm relay will then be activated and the switch can be released. After about 5 seconds, the alarm relay will turn off and the status light will alternate slowly between green and amber while the self test executes The controlling software simulates a 3000 ppm CO environment and causes the unit to alarm after approximately one minute has elapsed. When this happens, the status light turns red and the buzzer will sound two complete alarm cycles. The unit will then return to normal operation.

3.) If the CM-S1 is in an alarm condition due to the detection of carbon monoxide, one push of the switch will cause the alarm buzzer to mute for five minutes. After the five-minute period, if CO is still present, the status light will again switch to RED, the alarm relay will close and the buzzer will sound.

TROUBLE INDICATOR

The CM-S1’s status LED is normally illuminated with a green color. To indicate a “trouble” condition, the CM-S1 status LED will flash AMBER and the CM-S1 buzzer will emit a short "chirp" every 50 seconds. See ERRORS below. The CM-S1 computer continuously monitors various detector parameters. Failure of the CM-S1’s internal power supply, or a lack of power to the detector will result in the status light remaining OFF (not illuminated). In this case, the most common cause of detector trouble would be a break in the wiring between the control panel and the CM-S1. The CM-S1 does NOT provide a trouble signal to the alarm panel.

ERRORS

The computer in the CM-S1 continuously monitors various operating parameters. If a problem is found, the unit will switch to Trouble mode. See TROUBLE INDICATOR above. To reset the unit for normal operation, press the TEST/RESET switch, or remove power to the unit, wait a few seconds, then re-apply unit power. If this problem persists, your detector requires repair; contact the alarm panel installer or Macurco Tech Support for advice. If repair is required, return the unit to manufacturer to comply with warranty.

MAINTENANCE

The CM-S1 should be tested monthly by pushing the TEST/RESET switch; see TEST/RESET switch, above. At the same time, the CM-S1 should be cleaned using the soft brush attachment of your vacuum cleaner. The CM-S1 should be tested after cleaning to ensure the unit is operating normally. There are no field calibration procedures for this unit.

SENSOR POISONS

The gas sensor in the detector is designed with extreme sensitivity to the environment. As a result, the CO sensor may be damaged if it is exposed to a direct spray from aerosols such as paints, silicone vapors, etc., or to a high density of corrosive gases such as hydrogen sulfide or sulfur dioxide for an extended period of time. The sensor may react to chemicals such as ammoniated cleaning agents, volatile solvents and hydrogen gas. In sufficient concentration, these chemicals may cause a false alarm.

LIMITED WARRANTY

Aerion Technologies Inc. (ATI), manufacturer of Macurco products, warrants the CM-S1 gas detector will be free from defective materials and workmanship for a period of five (5) years from date of manufacture (stamped on the unit), provided it is maintained and used in accordance with ATI’s instructions and/or recommendations. If any component becomes defective during the warranty period, it will be replaced or repaired free of charge, if the unit is returned in accordance with the instructions below. This warranty does not apply to units that have been altered or had repair attempted, or that have been subjected to abuse, accidental or otherwise. The above warranty is in lieu of all other express warranties, obligations or liabilities. THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR PURPOSE ARE LIMITED TO A PERIOD OF FINE (5) YEARS FROM THE PURCHASE DATE. ATI shall not be liable for any incidental or consequential damages for breach of this or any other warranty, express or implied, arising out of or related to the use of said gas detector. Manufacturer or its agent's liability shall be limited to replacement or repair as set forth above. Buyer’s sole and exclusive remedies are return of the goods and repayment of the price, or repair and replacement of non-conforming goods or parts. (The Uniform Commercial Code applicable in the State of Colorado shall govern.)

RETURN INSTRUCTIONS

Call (303) 781-4062 for a Return Authorization number. After receiving a Return Authorization number, carefully pack the detector with a written description of the nature of the return. Send the unit to the following address: Aerion Technologies Inc., Attn: Macurco Repair RA#_______,

6555 S. Kenton St., Ste. 304, Centennial, CO 80111.

Document #679-800-001

Page 3 of 4

Rev. 1.1, Jan 9, 2006

Page 3
Image 3
Macurco CM-S1 specifications RESET/SILENCE Switch, Trouble Indicator, Errors, Maintenance, Sensor Poisons, Limited Warranty

CM-S1 specifications

The Macurco CM-S1 is a sophisticated gas detection device designed to monitor and detect hazardous gases within various environments. Its primary focus is on safety, ensuring that users are alerted to potential dangers before they escalate into critical situations. The CM-S1 is widely used in commercial kitchens, laboratories, industrial settings, and other places where gas leaks may occur.

One of the standout features of the Macurco CM-S1 is its dual detection capability, allowing it to identify both carbon monoxide (CO) and natural gas (methane). This versatility makes it an invaluable tool for enhancing safety in various applications. The device employs advanced semiconductor technology for gas detection, which provides reliable and accurate readings, even in challenging conditions. The sensors are designed to deliver rapid response times, ensuring that any potentially harmful gas concentrations are detected almost immediately.

Another significant characteristic of the CM-S1 is its comprehensive digital display, which provides real-time data regarding gas levels and operational status. Users can see clear indicators of current gas concentrations, along with status updates that ensure optimal functioning. The device also features multiple alarm indicators, including audible, visual, and vibration alerts, ensuring that personnel are quickly made aware of any dangerous situations.

The Macurco CM-S1 is designed for easy installation and setup. It can be mounted on a wall or ceiling, providing flexibility depending on the specific environment. Additionally, the unit's compact design allows it to fit comfortably in various spaces without becoming obtrusive. The device is powered by a standard AC power supply, with a battery backup feature to ensure constant operation even during power outages.

For added convenience, the CM-S1 is equipped with user-friendly calibration and testing modes. This feature allows facility managers and safety personnel to conduct regular maintenance checks and adjustments, ensuring that the device remains fully functional.

In summary, the Macurco CM-S1 is an advanced gas detection solution that combines reliable performance with user comfort. Its cutting-edge technology, dual detection capability, and user-centric design make it an essential tool for safeguarding environments against potentially lethal gas leaks. Investing in the CM-S1 not only enhances safety but also promotes a proactive approach to hazard management in various settings.