WIRING DIAGRAMS
!ENSURE POWER IS OFF WHEN CONNECTING THE PIGTAIL CABLE TO THE
TYPICAL CONNECTION OF TWO
UL Listed Alarm Control Panel
N.O. initiating circuit
or current limit at 0.5 A for each
12/24V GND
SPDT
Alarm relay
GND 12/24V
N.O. | VIO | ||
SPDT | |||
N.C. | BLU | ||
Alarm | |||
COM | YEL | ||
relay | |||
| BLK | ||
| GND | ||
| RED | ||
| 12/24V | ||
|
|
N.O. VIO N.C. BLU COM YEL BLK RED
E.O.L.R.
1.The
2.The Alarm Control Panel (Fire or Fire/Burglar type or Critical Process Management Equipment) must be dedicated to CO detection or have alarm devices that provide a distinctive alarm for carbon monoxide detection. Do not connect the
3.The
4.The
5.LOCATION: Place the unit at a level where people breathe: about 5 feet (1.5 meters) above the floor. Mount the
6.SPACING: Use the same spacing as for smoke detectors – 30 foot (9 meters) centers, 900 sq. feet (83 sq. meters) per detector.
7.INSTALLATION: See page 1.
8.The alarm control panel zone inputs must be terminated with end of line resistors (E.O.L.R.), which are provided with the panel.
9.When using the
The
CM-S1 CONTROLLING A REMOTE ALARM
SPDT
Alarm relay
GND 12/24V
N.O. VIO N.C. BLU COM YEL BLK RED
Alarm Relay: SPDT,
1.0Amps., 60VDC, 60 VA dry contacts, no polarity
UL Listed Class 2
Power Source:
SPDT
Alarm relay
GND 12/24V
|
| UL | |
N.O. | VIO | LISTED | |
12VDC | |||
N.C. | BLU | ||
ALARM | |||
COM | YEL |
| |
| BLK |
| |
| RED |
| |
| UL LISTED |
| |
| 12VDC | POWER | |
| POWER SUPPLY |
Document | Page 4 of 4 | Rev. 1.1, Jan 9, 2006 |