The Monitor Mode provides for Real-Time display of Inverter operation. It also indicates the total number of Run events, Alarm and Fault events.

Accum Runs: Indicates the number of run commands given.

Accum Faults: Indicates the number of faults recorded.

Accum Alarms: Indicates the number of Alarms recorded.

- MONITOR MODE -

01/28/04 08:44:13

Run Status:

Stopped

Accum Runs:

0001

Accum Faults:

0001

Accum Alarms:

0000

- MONITOR MODE -

01/28/04 08:44:13

Last Flt: DC Bus UV 01/28/04 08:35 Last Alm: UL1 01/29/04 02:37

- MONITOR MODE -

01/28/04 08:44:13

U1-01: 000.00 Hz

U1-02: 000.00 Hz

U1-03: 000.00 A

U1-04: 0000

- MONITOR MODE -

01/28/04 08:44:13

U1-05: 000.00 Hz

U1-06: 000.0 VAC

U1-07: 000 VDC

U1-08: 000.0 Hp

- MONITOR MODE - 01/28/04 08:44:13

U1-09: 000.0 %Torque

U1-10: 00000000

U1-11: 00000000

U1-12: 00000000

- MONITOR MODE -

01/28/04 08:44:13

U1-13: 0000 H

U1-14: 0000

Date & Time:

Used to time stamp all history and trace data.

Run Status:

Indicates Running Forward, Running Reverse or Stopped.

Last Flt:

Indicates the last fault recorded w/time and date.

Last Alm:

Indicates the last alarm recorded w/time and date.

U1-01 = Frequency Reference

U1-02 = Output Frequency

U1-03 = Output Amps

U1-04 = Control Method

U1-05 = Motor speed

U1-06 = Motor Voltage

U1-07 = DC bus voltage

U1-08 = Output Hp

U1-09 = % Torque Output

U1-10 = Input terminal status

U1-11 = Output terminal status

U1-12 = Operation status

U1-13 = Run timer (hours)

U1-14 = Software ID

Impulse DataLogger Series 3 Instruction Manual

2/1/05

 

7 of 16