Underside Of Chimney
Figure 38
Chimney Section (S)
B |
A
*Part of Offset/Return Package Model
Figure 39
Note: See Framing and Dimension Chart for the sizes of the ceiling and roof openings. The size of the roof opening varies with the degree of pitch of the roof.
Offset Elbow AssemblyOffset elbows install the same as chimney sections. First, snap the inner section INTO the preceding inner section of flue. Check connection by pulling up slightly to ensure a tight fit. Next, the outer sections snap lock OVER the preceding outer section of chimney. Again, check outer section by pulling up slightly to ensure proper connection is made.
Return Elbow AssemblyReturn elbows install the same way as round terminations and stabilizers:
Step 1. Hold return elbow over top of last chimney section.
Step 2. Center inner slip section into inner flue
14
Step 3. Center
Step 4. Pull up slightly on return elbow to ensure locking joint has firmly engaged.
Step 5. Secure support straps to framing members by nailing under tension in sheer (Figure 40 ).
Return
Elbow
Figure 40
Note: The return elbow assembly performs the same function as a stabilizer. Consider this when determining the need for a stabilizer.
Note: Do not apply excessive pressure to any subsequent chimney section following return elbow assembly when installing. Ensure that each subsequent chimney section is securely attached by testing as noted above.
Combustion Air KitsThe installation of an outside combustion air kit is highly recommended. It is very important to ensure good fireplace operation in homes which are tightly weather sealed or have ventilating appliances installed.
Step 1. Determine the source for outside air, which can be installed through an outside wall or into a ventilated crawl space. In either case, a 4 1/2" diameter hole will be required for installation of the air inlet assembly.
CAUTION: AVOID INSTALLING THE AIR INLET WHERE THE OPENING COULD BE BLOCKED BY SNOW, BUSHES OR OTHER OBSTACLES. THE MAXIMUM HEIGHT FOR THE OUTSIDE AIR IS 50 FEET ABOVE THE HEARTH, PROVING THE AIR INLET IS TERMINATED A MINIMUM OF THREE (3) FEET BELOW THE CHIMNEY CAP LEVEL.
Note: Combustion air inlet ducts must not terminate in attic space.
Step 2. Install the air inlet eyebrow
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
AIR INLET
EYEBROW
ASSEMBLY
FOAK
Figure 41
Step 3. The air inlet for the outside air kit is located on the right hand side of the fireplace (Figure 42 ). Refer to the installation instructions packed with each
OPEN
CLOSED
Figure 42
After completing the installation of the optional combustion air vent system, the actuator arm must be put in service and tested to ensure proper operation before completing any enclosure around the firebox. Failure to do so may result in extensive and costly rework.
To operate, locate the hand operated
Operate the actuator through several cycles. Ensuring proper operation and freedom of movement. Return the actuator arm to the closed position.