6
clearances To comBusTiBlesWARNING: BE ABSOLUTELY SURE THE DISTANCE BETWEEN
THE HEATER AND THE SURFACE OF ANY COMBUSTIBLE
CONSTRUCTION IS NOT LESS THAN SHOWN.
Floor Protection
USA - The floor in front and under the heater must be pro-
tected with a minimum of 3/8” thick noncombustible material.
The covering must extend 16” in front of the door opening
of the heater and 8” to either side of the door opening and
5-1/2” to the rear or to the wall, whichever is smaller. In all
installations a 16” minimum hearth extension (in front of
the stove) is required as measured from the door opening
of the unit.
Canada - The floor in front and under the heater must be
protected with a minimum of 3/8” thick noncombustible
material. The covering must extend 457 mm in front of the
door opening of the heater and 200mm to either side of the
stove body and 200 mm to the rear or to the wall, whichever
is smaller. In all installations a 457mm minimum hearth
extension (in front of the stove) is required as measured
from the door opening of the unit.
Reduced Clearances
Clearances to combustible surfaces can be reduced with the
use of listed double wall connector pipe. See the clearances
with double wall pipe on the following page.
Alcove Clearances
Single Wall Pipe - Minimum 48"(1219mm) width, maxi-
mum 48" (1219mm) depth. Minimum ceiling height is 72”
(1829m).
Double Wall Pipe - Minimum 44"(1117mm) width, maxi-
mum 48" (1219mm) depth. Minimum ceiling height is 72”
(1829m).
Mobile Home Installations
All mobile home installations require an outside air kit (part #
71111 or 71112). The stove must be bolted to the floor and
grounded to the chassis of the mobile home.
WARNING: DO NOT INSTALL IN SLEEPING ROOM OF A
MOBILE HOME.
CAUTION: THE STRUCTURAL INTEGRITY OF THE MOBILE
HOME FLOOR, WALL, AND CEILING/ROOF MUST BE
MAINTAINED.
Approved Chimney* - Your stove is approved for use with
Class A, UL 103HT Chimney and double wall connector pipe
from Security™ Chimneys.
Clearances to connector pipe shall be measured from the
flue collar of the stove.
Chimney & Connector
Minimum 6" diameter, minimum 24 MSG black steel con-
nector pipe with listed factory-built chimney suitable for use
with solid fuels or masonry chimney. Horizontal connection
not tested, refer to local building codes for installation. Re-
strictions apply! Read instructions before installing.
Clearance dimensions are to 6” (152mm) flue collar. If a
single wall connector pipe with shield is used, a 1 inch air
space is needed between pipe and shield. Shield attaches
to rear of stove pipe and must run from stove top to ceiling.
Pipe shield shall be UL listed.
Residential chimney systems must be from the same brands
as listed for mobile homes but connector pipe may be double
wall, single wall or single wall with shield as listed above.
Connector pipe and chimney must be of the same brand.
Components Required For Installation
Legs AND Bottom Heat Shield or Pedestal Base.
If optional blower is NOT used, Rear Heat Shield Block Off
Plate shall be installed.
* Other approved chimney brands are Projet, Jakes Evans/GSW, Dura-vent,
Metal Fab, Ameri-Tec, Metalbestos and Industrial Chimney (ICC).