Master Bilt BMG/TMG 27, 80, 48, 74, 52 How To Change The Setpoint, HOW TO CHANGE a parameter value

Models: 52 74 48 80 BMG/TMG 27

1 17
Download 17 pages 43.57 Kb
Page 10
Image 10
HOW TO CHANGE THE SETPOINT

HOW TO CHANGE THE SETPOINT

HOW TO CHANGE a parameter value

LIST OF PARAMETERS

Here is a list of the parameters the value of which can be changed in the programming mode, as well as their ranges.

Display

Parameter

 

Master-Bilt’s

Symbol

Range

BMG/TMG Setting

 

SP

Temperature Set Point

SPL…SPH

35°F

HYS

Temperature Differential

1 to 255°F

5°

SPL

Minimum Temperature limit setpoint

-50…SPH

27°F

SPH

Maximum Temperature limit setpoint

SPH…120°

50°F

AHA

High Temperature Alarm

-50…120°

65°F

ALA

Low Temperature Alarm

50…120°

0°F

ATD

Temperature Alarm Delay

0…120min

30min

DFR

Number of Defrost Cycle per 24hr

0…24

Off Cycle

DLI

Defrost Termination Temperature

-50…120°

-

DTO

Maximum Defrost Duration

1…120min

30min

ELECTRICAL CONNECTIONS

The controller is provided with a screw terminal block to connect cables with a cross section up to 2,5 mm2. Before connecting cables make sure the power supply complies with the control’s requirements. Separate the probe cables from the power supply cables, the outputs and the power connections. Do not exceed the maximum current allowed on each relay, in case of heavier loads use a suitable external relay or contactor’s.

PROBE CONNECTIONS

The probes shall be mounted with the bulb upwards to prevent damage due to casual liquid infiltration. It is recommended to place the thermostat probe at the warmest loacation of return air streams to correctly measure the average room temperature. Place the defrost termination probe among the evaporator fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during defrost, to prevent premature defrost termination.