Air Output, Air Intake, and Lint Filters

Air Output, Air Intake, and Lint Filters

1.Remove upper shell (see page 10).

2.Remove filter end cover screws using 5/16" nut- driver.

3.Remove filter end cover.

4.Replace air output and lint filters.

5.Wash or replace air intake filter (see Preventative Maintenance Schedule, page 8).

6.Replace filter end cover.

7.Replace fan guard and upper shell.

IMPORTANT: Do not oil

filters.

Pump Pressure

Adjustment

1.Remove pressure gauge plug from filter end cover.

2.Install accessory pressure gauge (part number HA1180).

3.Start heater (see Operation, page 7). Allow motor to reach full speed.

4.Adjust pressure. Turn relief valve to right to increase pressure. Turn relief valve to left to decrease pressure. See specifications at right for correct pressure for each model.

5.Remove pressure gauge. Replace pressure gauge plug in filter end cover.

12

Air Intake Filter

 

Filter End

 

Cover

Fan Guard

 

Lint Filter

Air Output

Filter

Figure 14 - Air Output, Air Intake, and Lint Filters,

70,000 BTU/Hr Model

Air Intake Filter

Filter End

Fan Guard

Cover

 

Lint Filter

Air Output

Filter

Figure 15 - Air Output, Air Intake, and Lint Filters,

100,000/150,000 BTU/Hr Models

(70,000 BTU/Hr Model Shown)

Pressure

Relief

Gauge

Valve

Plug

 

Figure 16PRESSURE- PressureGAUGEGaugePLUG PFA/OVPlug006BRemoval

 

 

Pump

Pressure

 

 

Gauge

Model

Pressure

 

70,000

BTU/Hr

4.5 PSI

 

100,000

BTU/Hr

4.5 PSI

 

150,000

BTU/Hr

4.9 PSI

 

Figure 17 - Adjusting Pump Pressure