5A. INSTALLATION INSTRUCTIONS 
5A.4 Installation of PEX-tubing Start the tubing installation by connecting 
the PEX tubing to the manifold. Loops can 
be pre-cut if you have figured the correct 
leader length (from the manifold to the 
actual heated area) when designing the 
system with our software. The Radiant 
Heating Tubing Requirements Report will 
give you the information to cut the loops 
from full rolls of tubing with the least 
amount of waste. 
Install the tubes by unrolling the coil and 
stepping the tubes into the tracks in the 
panels. Use hard shoes or a wooden piece 
on top of the tubes in order to fasten the 
tubes in the tracks. Be sure to use a block 
when using a hammer or mallet to set the 
tubing to avoid denting the aluminum 
surface. Follow the loop layout you have 
planned and connect the return tube to the 
manifold. It is very important that the tubes are snapped down completely into the tracks. 
When installing the tubing in the radius panels it is important to pull the tubing tightly around the 
bends. This will allow a space for tubing expansion during operation and greatly decrease the 
chance of noise during operation. When laying the tubing into the transition pieces we 
recommend using a bead of silicone adhesive to secure the tubing because the tubing is loose 
in these pieces. We recommend installation of the panel and tubing when ambient 
temperatures are above 40°F (4.5°C). 