Put power supply cord through the strain relief. Be sure that the wire insulation on the power supply cord is inside the strain relief. The strain relief should have a tight fit with the dryer cabinet and be in a horizontal position. Do not further tighten strain relief screws at this point.

Put direct wire cable through the strain relief. The strain relief should have a tight fit with the dryer cabinet and be in a horizontal position. Tighten strain relief screw against the direct wire cable.

Style 2: Direct wire strain relief

Unscrew the removable conduit connector and any screws from a ³⁄₄" (1.9 cm) UL listed strain relief (UL marking on strain relief). Put the threaded section of the strain relief through the hole below the terminal block opening. Reaching inside the terminal block opening, screw the removable conduit connector onto the strain relief threads.

A

B

C

A. Removable conduit connector

B. Hole below terminal block opening

C. Strain relief threads

4.Now complete installation following instructions for your type of electrical connection: 4-wire(recommended)

3-wire(if 4-wire is not available)

Electrical Connection Options

If your home has:

And you will be

Go to Section

 

connecting to:

 

4-wire receptacle

A UL listed, 120/240-

4-wire connection:

(NEMA Type 14-30R)

volt minimum,

Power supply cord

 

30-amp, dryer power

 

 

supply cord*

 

4-wire direct

A fused disconnect or

4-wire connection:

 

circuit breaker box*

Direct Wire

5"

 

 

(12.7 cm)

 

 

3-wire receptacle

A UL listed, 120/240-

3-wire connection:

(NEMA type 10-30R)

volt minimum,

Power supply cord

 

30-amp, dryer power

 

 

supply cord*

 

3-wire direct

A fused disconnect or

3-wire connection:

 

circuit breaker box*

Direct Wire

3¹⁄₂"

 

 

(8.9 cm)

 

 

*If local codes do not permit the connection of a cabinet-ground conductor to the neutral wire, go to “Optional 3-wire connection” section.

11

Page 11
Image 11
Maytag W10139629A manual Style 2 Direct wire strain relief