4. ELECTRICAL ENGINEERING

The electrical study for the implementation of a CleanWavefilter is very easy. The few instructions described in this document must however be respected in order to ensure the safety and efficiency of the system.

4.1.ELECTRICAL SCHEMATIC

D1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CleanWave

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Z0

 

 

 

 

 

 

 

Non

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

linear

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 6

In order to minimise the disturbing currents in the installation, the CleanWave® filter should be placed close to the disturbing load.

4.2.ELECTRICAL PROTECTIONS

The CleanWavefilter must be protected in a similar way as a transformer.

As a standard rule, the electrical protection D1 must be a tetrapolar circuit breaker ( 3 phases + neutral ) with neutral over-current detection.

If such a protection is not possible (e.g. when the neutral and earth connectors are common (PEN)), a tripolar breaker will be used and the PEN conductor section will be doubled, as recommended in table 4.

The breakers must be selected according to the phase current as given in table 4 here above. The maximum inrush current is lower or equal to the nominal current and doesn't require particular precautions.

4.3.WIRING

The minimum recommended wiring sections for the different connectors are given in table 4. These are minimum recommendations according to the European regulations. Higher sections may be used according to local regulations, particularities of the electrical installation or specific rules.

The neutral conductor may be crossed by a current up to 1.8 times the phase current and is therefore over-sized.

MGE UPS SYSTEMS

CleanWave - Installation and user manual

Page 8/13

 

Version 2.1 - 21/04/05 - (JME)

 

Page 8
Image 8
MGE UPS Systems 12280 kVA user manual Electrical Engineering, CleanWave