MGE UPS Systems 700C, 1000C Shutdown, Output tab, Bypass tab, Operation, Personalisable function

Models: 1000C 700C

1 28
Download 28 pages 9.65 Kb
Page 20
Image 20
"Output" tab

3. Operation

"Output" tab

Personalisable function

Default setting

Options

 

 

 

Rated UPS voltage

230 V

200 V - 210 V - 220 V - 240 V

 

 

 

Rated UPS frequency

F = 50 Hz

60 Hz

 

 

 

UPS tolerance for AC-power

F ± 5%

F ± 1% to ± 10%, in 1% steps

source frequency

 

 

 

 

 

Overload alarm threshold

110%

0 to 110%, in 10% steps

 

 

 

UPS restart following short-circuit

Disabled

Enabled (click to add check)

 

 

 

"Bypass" tab

Personalisable function

Default setting

Options

 

 

 

Transfer to bypass if overload

Enabled

Disabled (click to remove check)

 

 

 

Transfer to bypass following a fault, whatever the

Disabled

Enabled (click to add check)

conditions on the AC-power source

 

 

 

 

 

3.5 Shutdown

bypass

Press button 23 (return to the OFF position).

The connected equipment is no longer supplied with power.

23

Page 20 - 51031604EN/AB

Page 20
Image 20
MGE UPS Systems 700C, 1000C Shutdown, Output tab, Bypass tab, Operation, Personalisable function, Default setting, Options