6.Performance & Product Specifications
120V model | NOVA 600 AVR | NOVA 1100 AVR |
UPS power rating | 600VA | 1100VA |
UPS power rating | 360W | 660W |
Input mains voltage range | ||
Output voltage in mains mode | ||
Output voltage in bat mode | 120V + | 120V + |
Output frequency in bat mode | 50/60Hz±1Hz | 50/60Hz±1Hz |
Deep discharge protection | 4 hours | 4 hours |
UPS backup time | 15 minutes for 1 sets PC | 15 minutes for 2 sets PC |
UPS output waveform | ||
Input/Output cord | NEMA 15A | NEMA 15A |
Input protection | Circuit breaker 10A/250V | Circuit breaker 20A/250V |
Recharge time | 8 hours to recover 80% after | 8 hours to recover 80% after |
| complete discharge | complete discharge |
Battery | Sealed lead acid battery | Sealed lead acid battery |
| 12V/7.2Ah x 1 | 12V/7.2Ah x 2 |
Surge rating (joule) | 175J | 175J |
Operating temperature | ||
Relative humidity | ||
Product size (D x W x H) | 13.8 * 4.9 * 5.6 inch | 14.8 * 6.7 * 7.4 inch |
Product weight | 15 Lbs | 27 Lbs |
7. Trouble Shooting
Condition | Item need to check |
| Check if the UPS is correctly plugged to the AC |
LED (green) is off, UPS has no output | power available and UPS is turned “ON” |
| |
| Charge UPS during 8 hours and try again. Consider |
UPS has little or no backup time | to replace battery if backup time is short. |
| Potential internal failure. Restart UPS. If red LED |
Red ON and beep keep alarm | still light, call for assistance. |
| UPS lightly or heavily overload, reduce load. Reset |
Red Blinking and 1 beep every 0.5 second | circuit breaker or change fuse on UPS if necessary |
| Faulty battery. Recharge battery. Replace battery if |
Red ON | fault reappears. |
Any information or advice, please visit our web sit at www.mgeups.com or contact MGE UPS SYSTEMS
8.DB-9 cable wiring for serial model