TABLE 3: PARTS SUPPLIED FOR CV UNITS WITH OPTIONAL HEAT
QTY | PART NO. | DESCRIPTION |
|
|
|
|
|
1 | 820/Y |
| |
|
| ||
823/Y |
| ||
|
|
| |
|
|
|
|
1 | 822/BR |
| |
|
| ||
826/BR |
| ||
|
|
| |
|
|
|
|
1 | AB144GRA7171844 | 844/GY |
|
|
|
|
|
1 | AB144WHT7171845 | 845/W |
|
|
|
|
|
2 | Isolation Relay |
| |
|
|
|
|
|
|
|
|
|
|
|
|
FIGURE 1: POWER & CONTROL WIRING LOCATION
FIGURE 2 : EXISTING CONTROL PANEL COMPO- NET LOCATION
FIGURE 3 : TYPICAL THERMOSTAT WIRING
OPEN ALL DISCONNECTS BEFORE SERVIC- ING THIS UNIT.
The new thermostat requires a thermostat cable with a mini- mum of 10 conductors that run from the
1.Locate the W7400 control module in the
2.Remove the following wires form the W7400 control module and from the unit.
•201/R
•208/BR
•254/GY
•252/Y
•257/Y
•248/GY
•240/Y
•244/0
•246/PR
NOTE: Wire ties will need to be removed to remove above wires.
3.Disconnect wire 204/BR from the TR terminals on the w7400 control module.
NOTE: These wires will be used with the new controls.
4.Disconnect thermostat wire from terminals
NOTE: This wire will be used with the new controls.
NOTE: STEPS 5 THROUGH 7 ARE FOR OPTIONAL HEAT ONLY.