Miller Electric Delta-Fab Connecting Input Power, Welding Power Source Input Power Connections

Models: Delta-Fab

1 32
Download 32 pages 60.77 Kb
Page 20
Image 20

3-14. Connecting Input Power

 

 

3

 

 

9

 

= GND/PE Earth Ground

 

 

 

 

 

8

 

 

 

11

 

 

 

10

 

 

 

 

2

4

 

 

 

7

 

 

 

 

 

1

 

 

 

IMPORTANT

 

 

6

3

 

 

Input Contactor

 

 

L1 (U)

 

 

7

L2 (V)

 

4

 

L3 (W)

 

 

 

 

5

4

 

 

 

3

 

 

 

 

 

 

= GND/ PE Earth Ground

Tools Needed: 3/8 in

3/8 in

YInstallation must meet all National and Local Codes − have only quali- fied persons make this installation.

YDisconnect and lockout/tagout in- put power before connecting input conductors from unit.

YMake input power connections to the welding power source first.

YAlways connect green or green/ yellow conductor to supply grounding terminal first, and never to a line terminal.

See rating label on unit and check input voltage available at site.

1Input Power Conductors (Customer Supplied Cord)

Select size and length of conductors using Section 3-12. Conductors must comply with national, state, and local electrical codes. If applicable, use lugs of proper amperage capacity and correct hole size.

Welding Power Source Input Power Connections

2 Strain Relief

Route conductors (cord) through strain re- lief and tighten screws.

3Machine Grounding Terminal

4Green Or Green/Yellow Grounding Conductor

5Reed Switch (Ground Current Sensor) (Optional)

Connect green or green/yellow grounding conductor to welding power source grounding terminal first. If unit is equipped with optional ground current sensor, route grounding conductor through reed switch two times and connect to grounding termi- nal.

6Welding Power Source Line Terminals

7Input Conductors L1 (U), L2 (V) And L3 (W)

Connect input conductors L1 (U), L2 (V) and L3 (W) to welding power source line terminals.

Close and secure access door on welding power source.

Disconnect Device Input Power Con- nections

8Disconnect Device (switch shown in OFF position)

9Disconnect Device (Supply) Grounding Terminal

Connect green or green/yellow grounding conductor to disconnect device grounding terminal first.

10 Disconnect Device Line Terminals

Connect input conductors L1 (U), L2 (V) And L3 (W) to disconnect device line terminals.

11 Over-Current Protection

Select type and size of over-current protection using Section 3-12(fused dis- connect switch shown).

Close and secure door on line disconnect device. Remove lockout/tagout device, and place switch in the On position.

800 103-C / Ref. 801 116-A

OM-2241 Page 16

Page 20
Image 20
Miller Electric Delta-Fab manual Connecting Input Power, Welding Power Source Input Power Connections