OM-2220 Page 12

2-5. Connecting Work Clamp and Gas/Air Supply

1 Work Clamp
2 Workpiece
Connect work clamp to a clean,
paint-free location on workpiece, as
close to cutting area as possible.
.Use only clean, dry air with 90
to 150 psi (620 to 1035 kPa)
pressure.
3 Gas/Air Inlet Opening
4 Hose
.Hose must have a minimum
inside diameter of 3/8 in
(9.5 mm).
5 Teflon Tape
Obtain hose with 1/4 NPT right-
hand thread fitting. Wrap threads
with teflon tape (optional) or apply
pipe sealant, and install fitting in
opening. Route hose to gas/air
supply.
Adjust gas/air pressure according
to Section 3-2.
Tools Needed:
5/8, 1-1/8 in
From Gas/Air Supply
3
5
1
2
4
ST-802 185 / Ref. SB-192 441
Rear o f U n i t

2-6. Electrical Service Guide

For any single or three phase voltage from 208 V to 575 V, the Amperes Input at

Rated Load Output is the same for 50 Hertz or 60 Hertz input power. For example,

the amperes input for 230 V, 50 Hz, single-phase input power is 33 amperes. The

amperes input for 230 V, 60 Hz, single-phase input power is also 33 amperes.

NOTE

60 Hz Models Single Phase Three Phase

Input Voltage 208 230 460 575 208 230 460 575
Input Amperes At Rated Output 36 33 16 13 21 20 9 8
Max Recommended Standard Fuse Rating In Amperes 1
Time-Delay 245 40 20 15 25 20 10 10
Normal Operating 3 50 50 25 20 30 30 15 10
Min Input Conductor Size In AWG/Kcmil 10 10 14 14 12 14 14 14
Max Recommended Input Conductor Length In Feet (Meters) 72
(22) 89
(27) 138
(42) 215
(66) 87
(27) 69
(21) 275
(84) 429
(131)
Min Grounding Conductor Size In AWG/Kcmil 10 10 14 14 12 14 14 14
Reference: 1999 National Electrical Code (NEC)
1 Consult factory for circuit breaker applications.
2Time-Delay fuses are UL class RK5 .
3Normal Operating (general purpose no intentional delay) fuses are UL class K5 (up to and including 60 amp), and UL class H ( 65 amp and
above).