Tag Addresses 2408
f
& 2404
f
PROFIBUS Communications Handbook
8-14 2408
f
& 2404
f
PROFIBUS Communications Handbook
Program General DataThe offsets of each parameter within the program general data block is given by the next table:
Address Offset Parameter
0 HoldbackType
0: None
1: Low
2: High
3: Band
1 HoldbackValue
2 Ramp Units
0: Secs
1: Mins
2: Hours
3 Dwell Units
0: Secs
1: Mins
2: Hours
4 Program Cycles
5Reserved
6Reserved
7Reserved
Program Segment DataProgram segment data is specified using 8 tag addresses, with the contents varying depending on the type of the segment. Theformat per segment is detailed in the following table, which gives the offset from the start of a segment data block for eachitem.
Address Offset Segment Types
STEP DWELL RAMP
RATE RAMP
TIME TO
TARGET
CALL END
0 Segment Type Segment Type Segment Type Segment Type Segment Type Segment Type
1 Target
Setpoint Target
Setpoint Target
Setpoint
2Duration Rate Duration
3 Program
Number End Type
4 Logic O/P’s Logic O/P’s Logic O/P’s Logic O/P’s Call Cycles Logic O/P’s
5
6
7
Example Address calculationsProgram 1, Segment 4, Segment Type = 8328 + 32 + 0 = 8360 (20A8 Hex)Program 2, Holdback Value = 8464 + 0 + 1 = 8465 (2111 Hex)Program 4 Segment 16, End Type = 8872 + 128 + 3 = 9003 (232B Hex)Power Level in End SegmentThis has the tag address 64 in 2400
f
controllers.Summary of Programmer Enumerators
Controller Display Parameter Description
Current Segment Type
0: End
1: Ramp (Rate)
2: Ramp (Time to target)
3: Dwell
4: Step
5: Call
End Segment Type
0: Reset
1: Indefinate Dwell
2: Set Output
Controller Display Parameter Description
Holdback Type
0: None
1: Low
2: High
3: Band
Dwell Units
0: Seconds
1: Minutes
2: Hours
Ramp Units
0: Seconds
1: Minutes
2: Hours