Mitsubishi Electronics installation manual Technical Data, Parameter E1032

Models: E1032

1 20
Download 20 pages 13.76 Kb
Page 11
Image 11

Technical Data

3Technical Data

Parameter

E1032

 

 

Front panel, W x H x D

202 x 187 x 6 mm

 

 

Mounting depth

56.9 mm (156.9 mm including clearance)

 

 

Front panel seal

IP 66

 

 

Rear panel seal

IP 20

 

 

Keyboard material

Membrane switch keyboard with metal domes. Overlay film

 

of Autotex F157 * with print on reverse side. 1 million

 

operations.

 

 

Reverse side material

Powder-coated aluminum

 

 

Weight

0.875 kg

 

 

Serial port RS422/

25-pin D-sub contact, chassis-mounted female with

RS485

standard locking screws 4-40 UNC.

 

 

Serial port RS232C

9-pin D-sub contact, male with standard locking screws 4-40

 

UNC.

 

 

Ethernet

Shielded RJ 45

 

 

USB

Host type A (USB 1.1), max output current 500 mA

 

 

Flash memory for

12 MB (incl. fonts)

application

 

 

 

Real time clock

±20 PPM + error because of ambient temperature and supply

 

voltage.

 

Total max error: 1 min/month at 25 °C

 

Minimum life of the real time clock battery: 3 years

 

Temperature coefficient: 0.004 ppm/°C2

Power consumption at

Normal: 0.15 A

rated voltage

Maximum: 0.35 A

 

 

Display

FSTN-LCD. 240 x 64 pixels, monocrome transflective.

 

LED backlight lifetime at the ambient temperature of

 

+25 °C: >50,000 h.

 

 

Active area of display,

127.0 x 33.8 mm

W x H

 

 

 

Fuse

Internal DC fuse, 2.0 AT, 5 x 20 mm

 

 

Power supply

+24V DC (20 - 30V DC). 3-pin jack connection block.

 

CE: The power supply must conform with the requirements

 

for SELV or PELV according to IEC 950 or IEC 742.

 

UL: The power supply must conform with the requirements

 

for class II power supplies.

 

 

Ambient temperature

Vertical installation: 0 ° to +50 °C

 

Horizontal installation: 0 ° to +40 °C

 

 

Storage temperature

-20 ° to +70 °C

 

 

Relative humidity

5 - 85 % non-condensed

 

 

EMC tests on the

The operator terminal conforms with the essential protection

operator terminal

requirements in article 4 of the directive 89/336/EEC. Noise

 

tested according to EN61000-6-3 emission and EN61000-6-2

 

immunity.

 

 

UL, cUL approvals

UL 1604 Class I, Div 2 / UL 508 / UL 50 4x indoor use only

(when product or

 

packing is marked)

 

 

 

DNV

Ceritfication in progress

 

 

NEMA

4x indoor use only

 

 

* See section Chemical Resistance for more information.

Mitsubishi Electric, MA00816