Installation

3.Secure the operator terminal in position, using all the fastening holes and the provided brackets and screws:

x 4

0.5 - 1.0 Nm

4. Connect the cables in the specified order.

ACaution

Ensure that the operator terminal and the controller system have the same electrical grounding (reference voltage level), otherwise errors in communication may occur.

BUse an M5 screw and a grounding conductor (as short as possible) with a cross-section of minimum 2.5 mm2.

CCaution

- Use only shielded communication cables.

- Separate high voltage cables from signal and supply cables.

DCaution

- The operator terminal must be brought to ambient temperature before it is started up. If condensation forms, ensure that the operator terminal is dry before connecting it to the power outlet.

- Ensure that the voltage and polarity of the power source is correct.

B

Controller

RS422/

RS485

RS232

C

24V DC

24V DC

D

A

Ethernet

5.Carefully remove the laminated film over the operator terminal display, to avoid static electricity that could damage the terminal.