F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
2-13
2.5 General specificationsl
Ambient temperature During operation: 0 to +50°C (0 to +40°C when extension interface is used)
During storage: -20 to +60°C
Ambient humidity During operation: 35 to 85%RH (Condensation shall not be allowed.)
Vibration resistance
In accor-
dance with
JIS B3501
and IEC
1131-2
Frequency Acceleration Amplitude
10 times in
each of X,
Y and Z
directions
(for 80
minutes)
When inter-
mittent 10-57Hz - 0.075mm
vibrations
are applied 57-150Hz 9.8m/s2-
When con-
tinuous 10-57Hz - 0.035mm
vibrations
are applied 57-150Hz 4.9m/s2 -
Impact resistance In accordance with JIS B3501 and IEC 1131-2 (147 m/s2, three times in
each of X, Y and Z directions)
Noise resistance By noise simulator whose noise voltage is 1,000 Vp-p, noise width is 1µs and
cycle is 30 to 100 Hz
Withstand voltage 500V AC for 1 minute Between all power terminals as a whole
and ground terminal
Insulation resistance 500V DC, 5M or more by megger
Grounding Class 3 grounding
Operating atmosphere Corrosive gas and much dusts shall not be detected.
Protection structure IP65F