70
Parameter list
Communication
549 Protocol selection 0, 1, 2 1 1 232
550 NET mode operation command
source selection 0, 1, 9999 1 9999 204
551 PU mode operation command source
selection 1, 2 1 2 204
PID
control
553 PID deviation limit 0 to 100.0%, 9999 0.1% 9999 261
554 PID signal operation selection 0 to 3, 10 to 13 1 0 261,
283
Current average
monitor
555 Current average time 0.1 to 1.0s 0.1s 1s 305
556 Data output mask time 0.0 to 20.0s 0.1s 0s 305
557 Current average value monitor signal
output reference current 0 to 500A/0 to 3600A *2 0.01/0.1A
*2
Rated
inverter
current
305
⎯563 Energization time carrying-over times (0 to 65535) 1 0 141
⎯564 Operating time carrying-over times (0 to 65535) 1 0 141
Multiple
rating
570 Multiple rating setting 0, 1 1 0 86
⎯571 Holding time at a start 0.0 to 10.0s, 9999 0.1s 9999 104
⎯573 4mA input check selection 1, 2, 3, 4, 9999 1 9999 182
PID control
575 Output interruption detection time 0 to 3600s, 9999 0.1s 1s 261,
283
576 Output interruption detection level 0 to 400Hz 0.01Hz 0Hz 261,
283
577 Output interruption cancel level 900 to 1100% 0.1% 1000% 261,
283
Pump function
578 Auxiliary motor operation selection 0 to 3 1 0 283
579 Motor connection function selection 0 to 3 1 0 283
580 MC switching interlock time 0 to 100s 0.1s 1s 283
581 Start waiting time 0 to 100s 0.1s 1s 283
582 Auxiliary motor connection-time
deceleration time 0 to 3600/360s, 9999 0.1/0.01s 1s 283
583 Auxiliary motor disconnection-time
acceleration time 0 to 3600/360s, 9999 0.1/0.01s 1s 283
584 Auxiliary motor 1 starting frequency 0 to 400Hz 0.01Hz 60Hz 283
585 Auxiliary motor 2 starting frequency 0 to 400Hz 0.01Hz 60Hz 283
586 Auxiliary motor 3 starting frequency 0 to 400Hz 0.01Hz 60Hz 283
587 Auxiliary motor 1 stopping frequency 0 to 400Hz 0.01Hz 0Hz 283
588 Auxiliary motor 2 stopping frequency 0 to 400Hz 0.01Hz 0Hz 283
589 Auxiliary motor 3 stopping frequency 0 to 400Hz 0.01Hz 0Hz 283
590 Auxiliary motor start detection time 0 to 3600s 0.1s 5s 283
591 Auxiliary motor stop detection time 0 to 3600s 0.1s 5s 283
⎯611 Acceleration time at a restart 0 to 3600s, 9999 0.1s 5/15s *2 152
Speed
smoothing
control
653 Speed smoothing control 0 to 200% 0.1% 0 170
654 Speed smoothing cutoff frequency 0 to 12 0Hz 0.01H z 20Hz 170
⎯665 Regeneration avoidance frequency
gain 0 to 200% 0.1% 100% 298
Function Parameters
Name Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting