FX2N-8AD Analog input block Buffer Memory (BFM) 8
8-5
#32
Operating time 0 to 64,800 (s)
After that, 64,800 is kept.
Measurement starts when power is turned on, and measured value
is reset when power is turned off.
K0
#33 Thermo-couple disconnection detection(V1.10 or higher.)
It executes the disconnection detection with K1.
It automatically returns to K0 after i t completes it.
K0
Reserved 
#41 CH1 offset data (mV or µA) ¡K0 at shipment
#42 CH2 offset data (mV or µA) ¡K0 at shipment
#43 CH3 offset data (mV or µA) ¡K0 at shipment
#44 CH4 offset data (mV or µA) ¡K0 at shipment
#45 CH5 offset data (mV or µA) ¡K0 at shipment
#46 CH6 offset data (mV or µA) ¡K0 at shipment
#47 CH7 offset data (mV or µA) ¡K0 at shipment
#48 CH8 offset data (mV or µA) ¡K0 at shipment
Reserved 
#51 CH1 gain data (mV or µA) ¡K5000 at shipment
#52 CH2 gain data (mV or µA) ¡K5000 at shipment
Table 8.1: BFM Lists
BFM
No. Description Hold against
power failure Initial value