FX2N-8AD Analog input block Buffer Memory (BFM) 8
8-25

8.2.12 BFM #29: Error status

The error information is assigned to each bit of BFM #29.

Table 8.6: Bit assignment in BFM #29
Bit
No. Assignment Description
b0 Error detected b0 is ON while either one among b1 to b4 is ON.
b1 Offset/gain set value error Offset/gain value is outside setting range.
Set a correct value.
b2 Power error 24 V power is not normally supplied.
Check wiring and supply voltage.
b3 Hardware error FX2N-8AD may have failed.
Contact Mitsubishi Electric System Service nearest to you.
b4 A/D conversion value error A/D conversion value is abnormal.
Using scale over data (BFM #28), check channel in which error has
occurred.
b5 Thermocouple being
warmed up This bit is ON for 20 minutes after power is turned on.
b6 BFM read/write disabled This bit is ON during input characteristics change processing.
While this bit is ON, correct A/D data cannot be read from or written
to BFM.
b7 
b8 Set value error detected This bit is ON while either bit among b9 to b15 is ON.