825
FX3G/FX3U/FX3UC Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
37 Operation of Special Devices (M8000 -, D8000 -)
37.1 Special Device List (M8000 -, D8000 -)
31
FNC275-FNC279
Data
Transfer 3
32
FNC280-FNC289
High Speed
Processing 2
33
FNC290-FNC299
Extension File
Register
34
FNC300-FNC305
FX
3U
-CF-ADP
35
SFC•STL
Programming
36
Interrupt
Function
37
Special Device
38
Error Code
A
Version Up
Information
B
Execution Times
High Speed Counter Comparison, High Speed Table, and Positioning [Positioning is supported in FX3G, FX1S, FX1N, and FX1NC PLCs.]
M 8130 HSZ (FNC 55)instruction: Table comparison mode 3 3
D8130
––33
[M]8131 HSZ (FNC 55)instruction:
Table comparison mode completion flag 3 3 ––33
M 8132 HSZ (FNC 55) and PLSY (FNC 57) instructions: Speed
pattern mode 3 3 D8131 to
D8134
––33
[M]8133 HSZ (FNC 55) and PLSY (FNC 57) instructions: Speed
pattern mode completion flag 3 3 ––33
[M]8134
Not used
– – –––– –
[M]8135 – – –––– –
[M]8136 – – –––– –
[M]8137 – – –––– –
[M]8138 HSCT (FNC280) instruction:
Instruction execution complete flag 3 3 D8138 – – –
[M]8139
HSCS(FNC 53), HSCR(FNC 54), HSZ(FNC 55),
HSCT(FNC280) instructions:
High speed counter comparison instruction executing
3 3 D8139 – – –
M 8140 ZRN (FNC156) instruction:
CLR signal output function enable – – ––33 3
[M]8141
Not used
– – –––– –
[M]8142 – – –––– –
[M]8143 – – –––– –
[M]8144 – – –––– –
M 8145 [Y000] Pulse output stop command 3––33 3
M 8146 [Y001] Pulse output stop command 3––33 3
[M]8147 [Y000] Pulse output monitor (BUSY/READY) 3––33 3
[M]8148 [Y001] Pulse output monitor (BUSY/READY) 3––33 3
[M]8149 Not used – – –––– –
Inverter Communication Function (Refer to Data Communication Edition for details.)
[M]8150 Not used – – –––– –
[M]8151*1 Inverter communication in execution [ch1] 3*3 3 3 D8151 – – –
[M]8152*1 Inverter communication error [ch1] 3*3 3 3 D8152 – – –
[M]8153*1 Inverter communication error latch [ch1] 3*3 3 3 D8153 – – –
[M]8154*1 IVBWR (FNC274) instruction error [ch1] 3 3 D8154 – – –
[M]8154 Defined per use of EXTR (FNC180) – – ––
3*2 3*2
[M]8155 EXTR (FNC180) is using communicating port – – D8155 3*2 3*2
[M]8156*1 Inverter communication in execution [ch2] 3*3 3 3 D8156
[M]8156 Communication error or parameter error in EXTR
(FNC180) instruction – – D8156 3*2 3*2
[M]8157*1
Inverter communication error [ch2] 3*3 3 3 D8157
Communication error in EXTR (FNC180) instruction is
latched. – – D8157 3*2 3*2
[M]8158*1 Inverter communication error latch [ch2] 3*3 3 3 D8158 – – –
[M]8159*1 IVBWR (FNC274) instruction error [ch2] 3 3 D8159 – – –
*1. Cleared when PLC switches from STOP to RUN.
*2. Available in Ver. 3.00 or later.
*3. Available in Ver. 1.10 or later.
Number and name Operation and function
Applicable model
FX
3G FX3U
FX
3UC
Correspond-
ing special
device
FX
1S
FX
1N
FX
2N
FX
1NC
FX
2NC