9 - 9

MELSEC-F
WHEN COMMUNICATING DATA USING THE MC PROTOCOL9

9 - 9

NOTE

The following example shows the designation of the subheader to the monitoring

timer when communicating using MC protocol under the following conditions.

(Designated value)

(1) Format when communicating in binary code

(a) The order when sending a command (external device Ethernet module)

(b) The order when receiving a response (external device Ethernet module)

Target station : FX3U/FX3UC series to which FX3U-ENET-L is connected : FFH
Function used : Device memory batch read (bit units) : 00H
Monitoring timer value : 2500 ms : 000AH
Application data
00 FF 0AH00H64H00H00H00H20H4DH08H00HHH
Header
(M)
(H) (L) (H) (L) (H)
(L)
Subheader PC number Monitoring
timer Character field (command)
(Head device number) (Device name) Number of
device points
(Local station) (2500 ms) (8 points)
(100)
80H00H10H10H01H10H
M100(ON) M107(OFF)
M101(OFF) M106(ON)
M102(ON) M105(ON)
M103(OFF) M104(OFF)
Application data
Header
Subheader Complete
code
Character field (response)
on/off status of the
designated device
(Normal
completion)