3 - 19
MELSEC-F
SPECIFICATIONS3
3 - 19
(Continued from the previous page)
BFM number
Attribute Application Name
Initial value
Decimal
(Hexadecimal)
Flash ROM
save
Reference
section
Decimal
(Hexadecimal)
1610
(64AH)R/W
For fixed buffer
communication
Fixed buffer
communication
Transmission/
reception
request/Execution
result
When sending request or reception complete
confirmation signal of connection No.1
For sending
1) Write value
0001H: Sending request
2) Read value
0001H: Transmission ready
0002H: Between data being sent to while
waiting for a response (only when
procedure exists)
0004H: Stored when transmission
complete If instantly receiving the
next data, depending on the
timing of FROM instruction, 0001H
is stored without reading 0004H
0008H: Stored when transmission error
0000H: Stored when the open processing
or close processing is completed
For receiving
1) Write value
2) Read value
0
(0000H)
Chapter 6,
Chapter 7
1611
(64BH)R/W When sending request or reception complete
confirmation signal of connection No.2 (Same as connection No.1)
1612 to 1663
(64C to 67FH) System area
Write value Procedure No procedure
0002H
Response
transmission
to an
external
device
Allows the
following data
to be received
Read value Procedure No procedure
0001HAt data reception
0004H
Response
transmission
complete
Acceptance
for the data
reception
complete
0008H
Receiving process cannot be
normally completed
0000H
Stores after open/close