9 - 27

MELSEC-F
WHEN COMMUNICATING DATA USING THE MC PROTOCOL9

9 - 27

NOTE

C200 to C255 (Current Values) Batch Read

Since C200 to C255 are 32 bit devices, the device points should be specified as

twice as much as the points actually read.

Also, make sure that the device points are specified by an even number.

If they are specified by an odd number, the batch read cannot be performed. (Error

code 57H will be stored)

Example) When 32 devices are read at one access from C220 to C251 in the PLC

on which the Ethernet module is mounted.

(1) When communicating in binary code
*
01
H
FF
H
L
0A
H
H
00
H
*
81
H
00
H
43
H
4E
H
DC
H
00
H
00
H
00
H
40
H
00
H
4E
H
61
H
BC
H
00
H
40
H
01
H
B9
H
02
H

12345678=00BC614E

H

45678912=02B90140

H
CN220
Low
16bit
High
16bit
Low
16bit
High
16bit
L - H L - H L - H L - HL - - - - H
(Data name)
External
device side
(Example)
(Data name)
PLC side
(Example)
PC No.
Subheader
4 bytes x 32=128 bytes
Monitoring
timer
Head deviceNumber of device pointsHead data
Subheader
Last data
Complete code
32 points x 2 = 64 word