Checking code Meaning, detecting method Cause Checking method & Countermeasure
<Other than THHS>
1A short in the thermistor or
an open circuit was sensed.
The outdoor unit switches to
the temporary stop mode
with restarting after 3 min-
utes, then if the temperature
detected by the thermistor
just before restarting is in the
normal range, restarting
takes place.
2If a short or open circuit in
the thermistor is detected
just before restarting, error
code 5101, 5102, 5105,
5106, "5107", 5108 or
5109 is di s played.
3In the 3 minute restart mode,
the abnormal stop delay LED
is displayed.
4The above short or open cir-
cuit is not detected for 10
minutes after the compres-
sor starts, or for 3 minutes
during defrosting or after re-
covery following defrosting.
<THHS>
If a heat sink (THHS) tempera-
ture of -40°C is detected just
after the inverter starts or during
inverter operation.
1When pressue sensor de-
tects 1kg/cm2 or less during
operation, outdoor unit once
stops with 3 minutes restart-
ing mode, and restarts if the
detected pressure of pres-
sure sensor exceeds 1kg/
cm2 imediately before re-
starting.
2If the detected pressure of
sensor is less than 1kg/cm2
immediately before restart-
ing, error stop is com-
menced displaying 5201.
3Under 3 minutes restarting
mode, LED displays inter-
mittent fault check.
4During 3 minutes after com-
pressor start, defrosting and
3 minutes after defrosting
operations, trouble detec-
tion is ignored.
Discharge
(TH1)
Low
pressure
saturation
(TH2)
Liquid
pipe (TH5)
Ambient
tempera-
ture (TH6)
SC coil
outlet
(TH7)
SC coil
bypass
outlet
(TH8)
Radiator
panel
(THHS)
Pressure
sensor
trouble
5101
5102
5105
5106
5107
5108
5110
5201
Check the thermistors resistance.
Check if the lead wires are pinched.
Check for tearing of the insulation.
Check if a pin is missing on the con-
nector.
Check if a wire is disconnected.
Check the temperature picked up by
the sensor using the LED monitor.
If the deviation from the actual tem-
perature is great, replace the MAIN
circuit board.
(In the case of the THHS, replace
the INV board.)
1) Thermistor
2) Lead wires are being pinched.
3) Insulation is torn.
4) A connector pin is missing, or there
is faulty contact.
5) A wire is disconnected.
6) The thermistor input circuit on the
MAIN circuit board is faulty.
(In the case of the THHS, replace
the INV board.)
Thermal Sensor Error, Outdoor Unit
Short Circuit Detection Open Circuit Detection
TH1 240°C or higher (0.57 k)15°C or lower (321 k)
TH2 70°C or higher (1.71 k) -40°C or lower (399 k)
TH3 70°C or higher (1.14 k) -40°C or lower (130 k)
TH4 70°C or higher (1.14 k) -40°C or lower (130 k)
TH5 110°C or higher (0.4 k) -40°C or lower (130 k)
TH6 110°C or higher (0.4 k) -40°C or lower (130 k)
TH7 70°C or higher (1.14 k) -40°C or lower (130 k)
TH8 110°C or higher (0.4 k) -40°C or lower (130 k)
THHS 100°C or higher (3.0 k)-40°C or lower (2.5 k)
1) Pressutre sensor trouble.
2) Inner pressure drop due to a leak-
age
3) Broken cover.
4) Coming off of pin at connector por-
tion, poor contact.
5) Broken wire
6) Faulty thermistor input circuit of
MAIN board.
See Troubleshooting of pressure
sensor.
-
73
-