21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
1010100000
0110100000
1110100000
0001100000
1001100000
0101100000
1101100000
0011100000
1011100000
0111100000
1111100000
0000010000
1000010000
0100010000
1100010000
0010010000
1010010000
0110010000
1110010000
0001010000
1001010000
0101010000
1101010000
0011010000
1011010000
0111010000
1111010000
0000110000
1000110000
0100110000
1100110000
High
Pressure
Error 1, 2
Suction
Pressure
Error
TH1
Error
TH7
Error
No SW1 Item Display Remarks
12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8
Outdoor Unit
Preliminary Error
History
Error History 1
Inverter Error Detail
Error History 2
Inverter Error Detail
Error History 3
Inverter Error Detail
Error History 4
Inverter Error Detail
Error History 5
Inverter Error Detail
Error History 6
Inverter Error Detail
Error History 7
Inverter Error Detail
Error History 8
Inverter Error Detail
Error History 9
Inverter Error Detail
Error History 10
Inverter Error Detail
Type of Prelimi-
nary Inverter Error
(Details of the inverter
error in No. 17)
TH1 Data
TH2 Data
TH5 Data
TH6 Data
Low
Pressure
Error
Configuration
Detection
Error
TH2
Error
TH8
Error
Outlet
Tempera-
ture Error
Overcur-
rent
Protection
Reverse
Phase, Open
Phase Error
Heat Sink
Thermostat
Operation
TH5
Error
Refrigerant
Over-
charge
THHS
Error
HPS
Error
Overcur-
rent
Break
TH6
Error
0 ~ 9999
Inverter Error Detail (1 ~ 9)
0 ~ 9999
Inverter Error Detail (1 ~ 9)
0 ~ 9999
Inverter Error Detail (1 ~ 9)
0 ~ 9999
Inverter Error Detail (1 ~ 9)
0 ~ 9999
Inverter Error Detail (1 ~ 9)
0 ~ 9999
Inverter Error Detail (1 ~ 9)
0 ~ 9999
Inverter Error Detail (1 ~ 9)
0 ~ 9999
Inverter Error Detail (1 ~ 9)
0 ~ 9999
Inverter Error Detail (1 ~ 9)
0 ~ 9999
Inverter Error Detail (1 ~ 9)
0 ~ 9999
-99.9 ~ 999.9
-99.9 ~ 999.9
↑
↑
Lights up if an error
delay has occurred
between the time the
power was turned on
and the present time.
To turn the indicators
off, switch the power
OFF briefly.
E✻
The error and error
delay code are
displayed. If the
address and error
code are shown in
reverse, or there is
no error, “- - - -” is
displayed. E
If there is no error, “-
- - -” is displayed. E
E
If there is no error,
“- - - - ” is always
overwritten. E✻
E✻
No. 52 THHS
data are
monitored by
the inverter
microcomputer.
-
84
-