12-56
4122
[OPERATION ERROR]
•The dedicated instruction was executed to the
module mounted on the extension base unit in
the redundant system.
•The instruction for accessing the intelligent
function module mounted on the extension base
unit from the standby system at separate mode
was executed.
■Collateral information
•Common Information:Program error location
•Individual Information:–
■Diagnostic Timing
•When instruction executed
•Delete the dedicated instruction for the module
mounted on the extension base unit.
•Delete the instruction for accessing the intelligent
function module mounted on the extension base
unit from the standby system.
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/Continue
QnPRH*6
4130
[OPERATION ERROR]
Instructions to read SFC step comment
(S(P).SFCSCOMR) and SFC transition condition
comment (S(P).SFCTCOMR) are executed for the
comment file in ATA card
■Collateral information
•Common Information:Program error location
•Individual Information:–
■Diagnostic Timing
•When END/other instruction executed
Target comment file is to be other than the
comment file in ATA card.
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/
Continue*1
Qn(H)*4
QnPH*5
QnPRH
4131
[OPERATION ERROR]
The SFC program is started up by the instruction
while the other SFC program has not yet been
completed.
■Collateral information
•Common Information:Program error location
•Individual Information:–
■Diagnostic Timing
•When instruction executed
Check the SFC program specified by the
instruction. Or, check the executing status of the
SFC program.
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/Continue
QnU
4140
[OPERATION ERROR]
Operation where the input data is special value
("-0", unnormalized number, nonnumeric, ) is
performed.
■Collateral information
•Common Information:Program error location
•Individual Information:–
■Diagnostic Timing
•When instruction executed
Read the common information of the error using
the peripheral device, check the error step
corresponding to the numerical value (program
error part), and correct it.
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/
Continue*1
4141
[OPERATION ERROR]
Overflow occurs at operation.
■Collateral information
•Common Information:Program error location
•Individual Information:–
■Diagnostic Timing
•When instruction executed
Read the common information of the error using
the peripheral device, check the error step
corresponding to the numerical value (program
error part), and correct it.
4200
[FOR NEXT ERROR]
No NEXT instruction was executed following the
execution of a FOR instruction.
Alternatively, there are fewer NEXT instructions
than FOR instructions.
■Collateral information
•Common Information:Program error location
•Individual Information:–
■Diagnostic Timing
•When instruction executed
Read the common information of the error using
the peripheral device, check error step
corresponding to its numerical value (program error
location), and correct the problem.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
QCPU
Error
Code
(SD0)
Error Contents and Cause Corrective Action LED Status
CPU Status
Corresponding
CPU
*1 CPU operation can be set in the parameters at error occurrence. (LED indication varies.)
*4 The module whose first 5 digits of serial No. is "07012" or later.
*5 The module whose first 5 digits of serial No. is "07032" or later.
*6 The module whose first 5 digits of serial No. is "09012" or later.