
12-54
4102
[OPERATION ERROR]
In a multiple CPU system, the link direct device
(J \ ) was specified for the network module
under control of another station.
■Collateral information
•Common Information:Program error location
•Individual Information:–
■Diagnostic Timing
•When instruction executed
•Delete from the program the link direct device
which specifies the network module under
control of another CPU.
•Using the link direct device, specify the network
module under control of the host CPU.
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/
Continue*1
Q00/Q01*2
Qn(H)*2
QnPH
QnU*10
[OPERATION ERROR]
•The network No. or station No. specified for the
dedicated instruction is wrong.
•The link direct device (J \ ) setting is incorrect.
•The module No./ network No./number of
character strings exceeds the range that can be
specified.
■Collateral information
•Common Information:Program error location
•Individual Information:–
■Diagnostic Timing
•When instruction executed
Read the common information of the error using
the peripheral device, check error step
corresponding to its numerical value (program error
location), and correct the problem.
QCPU
[OPERATION ERROR]
•The specification of character string
(" ") specified by dedicated instruction cannot be
used for the character string.
■Collateral information
•Common Information:Program error location
•Individual Information:–
■Diagnostic Timing
•When instruction executed
QnU
4103
[OPERATION ERROR]
The configuration of the PID dedicated instruction
is incorrect.
■Collateral information
•Common Information:Program error location
•Individual Information:–
■Diagnostic Timing
•When instruction executed
Q00J/Q00/
Q01*2
Qn(H)
QnPRH
QnU
4105
[OPERATION ERROR]
PLOADP/PUNLOADP/PSWAPP instructins were
executed while setting program memory check.
■Collateral information
•Common Information:Program error location
•Individual Information:–
■Diagnostic Timing
•When instruction executed
•Del ete the program memory check setting.
•When using the program memory check, delete
PLOADP/PUNLOADP/PSWAPP instructions.
QnPH*5
4107
[OPERATION ERROR]
33 or more multiple CPU dedicated instructions
were executed from one CPU module.
■Collateral information
•Common Information:Program error location
•Individual Information:–
■Diagnostic Timing
•When instruction executed
Using the multiple CPU dedicated instruction
completion bit, provide interlocks to prevent one
CPU module from executing 33 or more multiple
CPU dedicated instructions.
Q00/Q01*2
Qn(H)*2
QnPH
Q00U/Q01U
Q02U
Error
Code
(SD0)
Error Contents and Cause Corrective Action LED Status
CPU Status
Corresponding
CPU
*1 CPU operation can be set in the parameters at error occurrence. (LED indication varies.)
*2 The function version is B or later.
*5 The module whose first 5 digits of serial No. is "07032" or later.
*10 The Universal model QCPU except the Q00UJCPU.