DCA-70USI (50 Hz) — GENERATOR OUTPUTS
Voltage Selector Switch
The voltage selector switch (Figure 16) is located above the output terminal panel’s Hard Wire
Generator OutputVoltages
A wide range of voltages are available to supply voltage for many different applications. Voltages are selected by using the voltage selector switch (Figure 15). To obtain some of the voltages as listed in Table 7 (see below) will require a fine adjustment using the voltage regulator (VR) control knob located on the control panel.
Table 7. Voltages Available
Three Phase | 208V | 220V | 240V | 416V | 440V | |
(Switchable) | ||||||
|
|
|
|
| ||
|
|
|
|
|
| |
Single Phase | 115V | 127V | 139V | 240V | 254V | |
(Switchable) | ||||||
|
|
|
|
| ||
|
|
|
|
|
|
Figure 16. Voltage Selector Switch
Voltage Selector Switch Locking Button
The voltage selector switch has a locking button to protect the generator and load from being switched while the engine is running. To lock the voltage selector switch, press and hold the red button located at the bottom of the switch.
CAUTION - CHANGINGVOLTAGES
NEVER change the position of the voltage selector switch while the engine is running. ALWAYS place circuit breaker in the open position before selecting voltage.
Generator Amperage
Table 8 describes the generator’s current output capability for both
Table 8. Generator Ampere Ratings
| kW | kVA | 100V | 200V | 220V | 440V |
|
|
|
|
|
|
|
Single Phase | 34.6 | N/A | 173A x 2 | N/A | 157A | N/A |
|
|
|
|
|
|
|
Three Phase* | 48 | 60 | N/A | 173A | 60A | 78A |
|
|
| * Power Factor = 0.8 |
|
|
PAGE 28 —