GENERATOR START-UP PROCEDURE
the problem. If the engine is running smoothly, place the engine speed switch (Figure 42) in the HIGH (up) position.
Figure 42. Engine Speed Switch (High)
5.Verify that the engine running status LED on the MPEC module (Figure 43) is lit (ON) after the engine has started.
9.The ammeter (Figure 47) will indicate zero amps with no load applied. When a load is applied, the ammeter will indicate the amount of current that the load is drawing from the generator.
Figure 47. Ammeter (No Load)
10.The engine oil pressure gauge (Figure 48) will indicate the oil pressure of the engine. Under normal operating conditions the oil pressure is approximately 42 to 71 psi. (290~490 kPa).
Figure 43. Engine Running (LED ON)
6.The generator’s frequency meter (Figure 44) should be displaying the 50 cycle output frequency in HERTZ.
Figure 44. Frequency Meter
7.The generator’s
Figure 45. Voltmeter Meter
8.If the voltage is not within the specified tolerance use the voltage adjustment control knob (Figure 46) to increase or decrease the desired voltage.
Figure 46. Voltage Adjust Control Knob
Figure 48. Oil Pressure Gauge
11.The coolant temperature gauge (Figure 49) will indicate the coolant temperature. Under normal operating conditions the coolant temperature should be between 167°~203°F (75°~95°C) (Green Zone).
Figure 49. Coolant Temperature Gauge
12.The tachometer gauge (Figure 50 will indicate the speed of the engine when the generator is operating. Under normal operating conditions this speed is approximately 1800 RPM’s.
Figure 50. Engine Tachometer Gauge
DCA70USI2 60 hz Generator • operation and parts manual — rev. #0 (06/28/11) — page 35