500kW Containerized Diesel Generator Set
Cooling System
Exhaust Manifold Type | Dry |
Radiator Design | Standard horizontal discharge |
Coolant Capacity - Engine | 6.3 gal. (24 L) |
|
|
Water Pump Design/Type | Belt Driven, Centrifugal |
Coolant Flow | 87 gal/min (329 L/min) |
Heat Rejection to Coolant | 7830 BTU/min (138 kW) |
|
|
Minimum Pressure Cap | 10 psi (70 kPa) |
Thermostat Range | |
|
|
Fuel System
Recommended Fuel | |||
|
|
| |
Fuel Pump Maximum Lift | 6.0 ft. (1.8 m) | ||
|
|
|
|
Filter Micron Size - 98% Efficiency |
| 2 |
|
|
|
| |
Total Fuel Flow | 112 gal./hr. (424 L/Hr.) | ||
Fuel Tank Capacity | 800 gal (3028 L) | ||
|
|
|
|
Fuel Consumption - gal/hr (L/hr) |
|
| |
Diesel Fuel @ % of Load | Standby |
| Prime |
25% | 11.6 (43.9) |
| 9.9 (37.4) |
|
|
|
|
50% | 18.8 (71.1) |
| 17.2 (65.3) |
|
|
|
|
75% | 25.7 (97.2) |
| 23.9 (90.5) |
100% | 34.4 (130.2) |
| 31.1 (117.8) |
|
|
|
|
Lubrication System
Type | Full Pressure System | ||
|
| ||
Oil Filters | |||
Oil Pan Capacity | 22 | gal. (83.0 | L) |
|
|
|
|
Oil Capacity with Filters | 24 | gal. (91.0 | L) |
|
| ||
Oil Pressure at Rated Speed (minimum) | 20 psi (138 kPa) | ||
|
|
|
|
Exhaust System
Exhaust Temperature at Rated kW | 875 oF (468 oC) |
Exhaust Flow at Rated kW | 3200 cfm (90.6 m3/min) |
Silencer Type | Critical |
Maximum Allowable Backpressure (standby) | 40.2 in/wc (10 kPa) |
|
|
Exhaust Outlet Size at | 5.0 in. (127 mm) |
DGC-2020 Digital Genset Controller
Digital Controller Features
■Local and Remote Generator Control
■Automatic and manual starting and stopping
■Engine and Generator Protection
■Programmable Analog Engine Senders
■ECU Communications via SAE J1939
■16 Programmable Contact Inputs
■Programmable Logic
■Automatic Transfer Switch Control (Mains Failure)
■Integrated RS485
■Auto Synchronizing
■Event recording
Monitoring
■Engine RPM
■Engine run time
■Generator voltage
■Generator current
■Generator frequency
■Oil pressure
■Battery voltage
■Fuel level measurements
■Running Hour Meter
■Coolant temperature
■Generator under/over voltage alarm/shutdown
■Generator under/over frequency alarm/shutdown
■Over Current alarm/shutdown
■Warm up and cooling functions
■Maintenance timer