750kW Containerized
Diesel Generator Set
Cooling System |
|
| |
Exhaust Manifold Type | Dry |
Radiator Design | Standard horizontal discharge |
Coolant Capacity - Engine and Radiator | 53 gal. (201 L) |
|
|
Water Pump Design/Type | Belt Driven, Centrifugal |
Coolant Flow | 235 gal/min (889.5 L) |
Heat Rejection to Coolant (Standby) | 27860 BTU/min (29.5 kW) |
Fan Horsepower | 42.7 hp (32.0 kW) |
|
|
Inteligen Digital Genset Controller
Fuel System |
|
|
|
|
|
| |
|
|
| |
Recommended Fuel | |||
|
|
|
|
Filter Micron Size - 98% Efficiency |
| 2 |
|
|
|
| |
Total Fuel Flow | 99 gal./hr. (374.7 L/Hr.) | ||
|
|
|
|
Fuel Consumption |
|
| |
Diesel Fuel @ % of Load | gal/hr |
| L/hr |
25% | 16.0 |
| 61 |
|
|
|
|
50% | 26.2 |
| 99 |
|
|
|
|
75% | 40.5 |
| 153 |
100% | 54.7 |
| 207 |
|
|
|
|
Exhaust System | Standby | Prime | |
Exhaust Temperature at Rated kW | 895 oF | 850 oF | |
(479.4 oC) | (454.4 oC) | ||
Exhaust Flow at Rated kW | 6160 cfm | 5546 cfm | |
(174.3 m3/min) | (157 m3/min) | ||
Silencer Type | Critical | ||
Maximum Allowable Backpressure | 41 in/wc (10.2 kPa) | ||
|
|
| |
Exhaust Outlet Size at | 2 x 8 in. | ||
|
|
|
Derating (60Hz)
The engine may be operated up to 5000 ft. | Altitude | Ambient | |
Temperature | |||
altitude and 95oF ambient temperature at the |
| ||
|
| ||
Standby rating, without derating . For | Above 5000ft. | Above 95°F | |
operation at higher altitudes and ambient | |||
temperatures, the power should be derated | derate at 4% | derate at 1% | |
according to the following factors: | per 1000 ft. | per 10°F | |
|
| ||
|
|
|
Digital Controller Features
■Large graphic
■Automatic and manual starting and stopping
■Phase sequence supervision
■Automatic shutdown/alarm function
■Input frequency
■Parameters adjustable via PC or iG keyboard
■Predefined and user definable configurations available. One configuration includes set of inputs/outputs and parameters
■Adjustable parameters for each configuration
■6 LED indicators
■Push buttons for simple control
■4 programmable outputs (out of 20 functions selection)
■4 binary configuration inputs
■Lamp test during start up
■Real time clock
■Sealed membrane panel to IP65
■180 x 113 mm front panel mounted case
■Speed measurement from magnetic pickup
■Oil pressure, Coolant temperature, Battery voltage and Fuel level measurements
■Running Hour Meter
■All Generator metering, kVAr, kW,
■Generator under/over voltage alarm/shutdown
■Generator under/over frequency alarm/shutdown
■Over Current alarm/shutdown
■Warm up and cooling functions
■
■Adjustable crank attempts
■Data logging
■Remote communications (RS232/Modbus)