Image 3
Cooling System

750kW Containerized

Diesel Generator Set

Cooling System

 

 

Exhaust Manifold Type

Dry

Radiator Design

Standard horizontal discharge

Coolant Capacity - Engine and Radiator

53 gal. (201 L)

 

 

Water Pump Design/Type

Belt Driven, Centrifugal

Coolant Flow

235 gal/min (889.5 L)

Heat Rejection to Coolant (Standby)

27860 BTU/min (29.5 kW)

Fan Horsepower

42.7 hp (32.0 kW)

 

 

Inteligen Digital Genset Controller

Fuel System

 

 

 

 

 

 

 

 

 

Recommended Fuel

ASTM-D975-No.1 or No. 2-D

 

 

 

 

Filter Micron Size - 98% Efficiency

 

2

 

 

 

 

Total Fuel Flow

99 gal./hr. (374.7 L/Hr.)

 

 

 

 

Fuel Consumption

 

 

Diesel Fuel @ % of Load

gal/hr

 

L/hr

25%

16.0

 

61

 

 

 

 

50%

26.2

 

99

 

 

 

 

75%

40.5

 

153

100%

54.7

 

207

 

 

 

 

Exhaust System

Standby

Prime

Exhaust Temperature at Rated kW

895 oF

850 oF

(479.4 oC)

(454.4 oC)

Exhaust Flow at Rated kW

6160 cfm

5546 cfm

(174.3 m3/min)

(157 m3/min)

Silencer Type

Critical

Maximum Allowable Backpressure

41 in/wc (10.2 kPa)

 

 

 

Exhaust Outlet Size at hook-up

2 x 8 in.

 

 

 

Derating (60Hz)

The engine may be operated up to 5000 ft.

Altitude

Ambient

Temperature

altitude and 95oF ambient temperature at the

 

 

 

Standby rating, without derating . For

Above 5000ft.

Above 95°F

operation at higher altitudes and ambient

temperatures, the power should be derated

derate at 4%

derate at 1%

according to the following factors:

per 1000 ft.

per 10°F

 

 

 

 

 

Digital Controller Features

Large graphic back-lit LCD display 128x64 pixel resolution

Automatic and manual starting and stopping

Phase sequence supervision

Automatic shutdown/alarm function

Input frequency 50-60 Hz

Parameters adjustable via PC or iG keyboard

Predefined and user definable configurations available. One configuration includes set of inputs/outputs and parameters

Adjustable parameters for each configuration

6 LED indicators

Push buttons for simple control

4 programmable outputs (out of 20 functions selection)

4 binary configuration inputs

Lamp test during start up

Real time clock

Sealed membrane panel to IP65

180 x 113 mm front panel mounted case

Speed measurement from magnetic pickup

Oil pressure, Coolant temperature, Battery voltage and Fuel level measurements

Running Hour Meter

All Generator metering, kVAr, kW, V1-V3, Hz, I1-I3, kWh, kVAh

Generator under/over voltage alarm/shutdown

Generator under/over frequency alarm/shutdown

Over Current alarm/shutdown

Warm up and cooling functions

Pre-lubrication function with timers

Adjustable crank attempts

Data logging

Remote communications (RS232/Modbus)