750kW Containerized
Diesel Generator Set
Cooling System | 
  | 
  | |
Exhaust Manifold Type  | Dry  | 
Radiator Design  | Standard horizontal discharge  | 
Coolant Capacity - Engine and Radiator  | 53 gal. (201 L)  | 
  | 
  | 
Water Pump Design/Type  | Belt Driven, Centrifugal  | 
Coolant Flow  | 235 gal/min (889.5 L)  | 
Heat Rejection to Coolant (Standby)  | 27860 BTU/min (29.5 kW)  | 
Fan Horsepower  | 42.7 hp (32.0 kW)  | 
  | 
  | 
Inteligen Digital Genset Controller
Fuel System | 
  | 
  | 
  | 
  | 
  | 
  | |
  | 
  | 
  | |
Recommended Fuel  | |||
  | 
  | 
  | 
  | 
Filter Micron Size - 98% Efficiency  | 
  | 2  | 
  | 
  | 
  | 
  | |
Total Fuel Flow  | 99 gal./hr. (374.7 L/Hr.)  | ||
  | 
  | 
  | 
  | 
Fuel Consumption  | 
  | 
  | |
Diesel Fuel @ % of Load  | gal/hr  | 
  | L/hr  | 
25%  | 16.0  | 
  | 61  | 
  | 
  | 
  | 
  | 
50%  | 26.2  | 
  | 99  | 
  | 
  | 
  | 
  | 
75%  | 40.5  | 
  | 153  | 
100%  | 54.7  | 
  | 207  | 
  | 
  | 
  | 
  | 
Exhaust System | Standby | Prime | |
Exhaust Temperature at Rated kW  | 895 oF  | 850 oF  | |
(479.4 oC)  | (454.4 oC)  | ||
Exhaust Flow at Rated kW  | 6160 cfm  | 5546 cfm  | |
(174.3 m3/min)  | (157 m3/min)  | ||
Silencer Type  | Critical  | ||
Maximum Allowable Backpressure  | 41 in/wc (10.2 kPa)  | ||
  | 
  | 
  | |
Exhaust Outlet Size at   | 2 x 8 in.  | ||
  | 
  | 
  | |
Derating (60Hz)
The engine may be operated up to 5000 ft.  | Altitude | Ambient | |
Temperature  | |||
altitude and 95oF ambient temperature at the  | 
  | ||
  | 
  | ||
Standby rating, without derating . For  | Above 5000ft.  | Above 95°F  | |
operation at higher altitudes and ambient  | |||
temperatures, the power should be derated  | derate at 4%  | derate at 1%  | |
according to the following factors:  | per 1000 ft.  | per 10°F  | |
  | 
  | ||
  | 
  | 
  | 
Digital Controller Features
■Large graphic 
■Automatic and manual starting and stopping
■Phase sequence supervision
■Automatic shutdown/alarm function
■Input frequency 
■Parameters adjustable via PC or iG keyboard
■Predefined and user definable configurations available. One configuration includes set of inputs/outputs and parameters
■Adjustable parameters for each configuration
■6 LED indicators
■Push buttons for simple control
■4 programmable outputs (out of 20 functions selection)
■4 binary configuration inputs
■Lamp test during start up
■Real time clock
■Sealed membrane panel to IP65
■180 x 113 mm front panel mounted case
■Speed measurement from magnetic pickup
■Oil pressure, Coolant temperature, Battery voltage and Fuel level measurements
■Running Hour Meter
■All Generator metering, kVAr, kW, 
■Generator under/over voltage alarm/shutdown
■Generator under/over frequency alarm/shutdown
■Over Current alarm/shutdown
■Warm up and cooling functions
■
■Adjustable crank attempts
■Data logging
■Remote communications (RS232/Modbus)