500kW Containerized Diesel Generator Set

APPLICATION DATA

Alternator Specifications

 

Make

Marathon Magna Max

Type

4-Pole, Rotating Field

Number of Leads

10 or 12

Generator Type

Rotating Field; PMG

Voltage Regulator

Solid State, Digital, Model DVR2000

Insulation

NEMA MG1-1.66

Material

Class H

Temperature Rise

Standby Rating: 125o C

Prime Rating: 105o C

 

Bearing: Number, Type

Single, Sealed

Coupling

Flexible Disk

Amortisseur Windings

Full

Voltage Regulation (no load to full load)

2% Maximum

One Step Load Acceptance % of rating per

100

NFPA-110

 

Peak Motor Starting HP

250

Generator Efficiency at Full Load

93%

Phase Sequence

ABC (L1, L2, L3)

L-L Harmonic Max Total

3.5%

L-L Harmonic Max Single

2.5%

Voltage Dip Upon Full Load Application (1 Step)

20% for 1.6 seconds

Voltage Rise Upon Full Load Rejection (1 Step)

14% for 0.6 of a second

The EGC500DD Sound Attenuated Generator is configured for standard 60 Hz, 208V and 480V output. Special voltage outputs are available (special order).

Alternator Features

All ratings tested per MIL-STD-705 as applicable.

Generator protection for overload and short circuit.

Generator is designed and built within NEMA, IEEE and ANSI standards for temperature rise.

PMG exciter for superior regulation and response.

Three phase sensing on regulator with EMI protection.

Skewed rotor for smooth voltage wave form.

Vacuum impregnated epoxy varnish - Fungus resistant per MIL-I-24092.

Sustain short circuit current at 300% of rated current up to 10 seconds.

Engine Specifications

 

Manufacturer/Model

Detroit Diesel 8V2000-G81

Engine Type

4-cycle, Turbocharged,

Air to Water Aftercooled

 

Cylinder Arrangement

V-8

Displacement

972 in3 (16 liter)

Bore

5.12 in. (130 mm)

Stroke

5.91 in. (150 mm)

Compression Ratio

14.5:1

 

 

Piston Speed (60Hz)

29.5 ft./sec. (9.0 m/sec)

Bearing Main: Number

5

Bearing Main: Type

Replaceable, Precision

 

 

Cylinder Block

Cast iron

 

 

Cylinder Head Material

Cast iron

Crankshaft Material

Forged steel

Valves

Dual, Poppet Type

 

 

Brake Mean Effective Pressure (BMEP)

346 psi (2385 Kpa)

Rated RPM (60 Hz)

1800

Max. Power At Rated RPM (with fan)

765 hp (570.5 kW)

 

 

Governor: Type

Electronic

Frequency Regulation: No load to full load

+0.10 Hz

Frequency Regulation: Steady State

+0.05 Hz

 

 

Air Cleaner Type - All Models

Dry, Dual Element

 

 

Amperage

Voltage

Phase

Power

Continuous Amperes

Factor

Standby

Prime

 

 

120/208

3

0.8

1734

1561

277/480

3

0.8

752

677

Engine Electrical System

Battery Charging Alternator Ground Type

Negative

 

 

Volts

24 VDC

 

 

Ampere Rating

70A

 

 

Starter Motor Rated Voltage

24 VDC

 

 

Minimum Recommended Battery for

800 Ah

0 °C / Cold Cranking Performance

 

Derating

 

 

Derating Factors (60 Hz)

Altitude

Ambient

Temperature

 

 

The engine may be operated up to 2000 ft.

 

 

altitude and 40oC ambient temperature at the

 

>40 oC =

Standby rating, without derating. For

>2000 m =

operation at higher altitudes and ambient

4% per 500 m

1.5% per 5 oC

temperatures, the power should be derated

 

 

according to the following factors:

 

 

EGC500DD Rev 2

Page 2
Image 2
Multiquip EGC500DD warranty Engine Specifications, Engine Electrical System, Derating, Alternator Features