500kW Containerized Diesel Generator Set
Cooling System
Exhaust Manifold Type | Dry |
Radiator Design | Standard horizontal discharge |
|
|
Coolant Capacity - Engine | 11.6 gal. (44 L) |
|
|
Coolant Capacity - Engine and Radiator | 42 gal. (159 L) |
Water Pump Design/Type | Belt Driven, Centrifugal |
Coolant Flow | 79 gal/min (299 L) |
|
|
Heat Rejection to Coolant | 11535 BTU/min (202.7 kW) |
Fan Horsepower | 23 hp (17 kW) |
Thermostat | 188.6 °F (87 °C) |
|
|
Fuel System |
|
|
|
|
|
| |
Recommended Fuel | |||
|
|
|
|
Fuel Pump Maximum Lift |
| 6.0 ft. (1.8 m) | |
Filter Micron Size - 98% Efficiency |
| 2 |
|
Total Fuel Flow | 186.1 gal./hr. (704.5 L/Hr.) | ||
|
|
|
|
Fuel Consumption |
|
| |
|
|
|
|
Diesel Fuel @ % of Load | gal/hr |
| L/hr |
25% | 10.1 |
| 38.2 |
50% | 18.1 |
| 68.5 |
|
|
|
|
75% | 26.8 |
| 101.4 |
100% | 37.7 |
| 142.7 |
|
|
|
|
Lubrication System |
|
|
|
|
|
| |
|
| ||
Type | Full Pressure System | ||
|
| ||
Oil Filters | 2 | ||
Oil Pan Capacity | 12.2 | gal. (46.0 | L) |
|
|
|
|
Oil Capacity with Filters | 14.3 | gal. (54.0 | L) |
|
| ||
Oil Pressure at Rated Speed | 47 - 57 psi (324 - 393 kPa) | ||
|
|
|
|
Exhaust System
Exhaust Temperature at Rated kW | 980 oF (527 oC) |
(Dry Exhaust) |
|
Exhaust Flow at Rated kW | 4080 cfm (115.5 m3/min) |
Silencer Type | Critical |
Maximum Allowable Backpressure | 41.1 in/wc (10.2 kPa) |
Exhaust Outlet Size at | 5.0 in. (127 mm) |
|
|
Inteligen Digital Genset Controller
Digital Controller Features
■Large graphic
■Automatic and manual starting and stopping
■Phase sequence supervision
■Automatic shutdown/alarm function
■Input frequency
■Parameters adjustable via PC or iG keyboard
■Predefined and user definable configurations available. One configuration includes set of inputs/outputs and parameters
■Adjustable parameters for each configuration
■6 LED indicators
■Push buttons for simple control
■4 programmable outputs (out of 20 functions selection)
■4 binary configuration inputs
■Lamp test during start up
■Real time clock
■Sealed membrane panel to IP65
■180 x 113 mm front panel mounted case
■Speed measurement from magnetic pickup
■Oil pressure, Coolant temperature, Battery voltage and Fuel level measurements
■Running Hour Meter
■All Generator metering, kVAr, kW,
■Generator under/over voltage alarm/shutdown
■Generator under/over frequency alarm/shutdown
■Over Current alarm/shutdown
■Warm up and cooling functions
■
■Adjustable crank attempts
■Data logging
■Remote communications (RS232/Modbus)
EGC500DD Rev 2