Multiquip MC-62S MC-62P/S CONCRETE MIXER - ELECTRIC MOTOR, Electric Motor, Voltage Change Switch

Models: MC-62P

1 120
Download 120 pages 12.84 Kb
Page 18
Image 18
MC-62P/S CONCRETE MIXER — ELECTRIC MOTOR

MC-62P/S CONCRETE MIXER — ELECTRIC MOTOR

Electric Motor

For maintenance care and operation of the electric motor, refer to your electric motor instruction booklet furnished with the electric motor.

Protect the electric motor from dust as much as possible and keep ventilating openings clean.

CAUTION:

DO NOT spray water at any time on the electric motor.

DO NOT operate electric motor in a explosive environment.

The electric motor used in this mixer is a single-phase 1.5 HP motor. The input voltage requirement for this motor is either 115 or 230 VAC only.

Electric Motor Connection

A 12 inch electrical cable (Figure 2) with a pigtail at one end is provided with the electrical motor for hookup to a power source. Table 1. shows the required NEMA connector for the desired motor horsepower rating. In addition, Table 2 also shows the matching NEMA approved connector for the required extension cord.

ALWAYS, make certain that the power source required for the electric motor is correct and always use the correct NEMA configuration plug. Failure to supply the correct voltage to the motor can severely damage the motor.

The electric motor supplied with the mixer is configured from the factoryfor115VACgroundedoperation.Makecertainthatthecorrect size grounded (3-wires) extension cord is used.See Table 5.

Motors can burn out when the line voltage falls 10% below the voltage rating of the motor. Failure to use proper voltage will cause the motor to overheat and actuate the overload switch.

If overload protection should actuate because of improper voltage or any other malfunction, turn the main switch on the motor to the "OFF" position and correct the problem, press the reset switch button, and turn the main switch to the "ON" position.

Table 5. Recommended Extension Cord Sizes

Electric

Input

50 ft.

75 ft.

100 ft.

200 ft.

Motor

Voltage

(15.24 m)

(22.86 m)

(30.48 m)

(60.96 m)

 

 

 

 

 

 

 

115 VAC

No. 12

No. 10

No. 8

No. 6

1.5 HP

 

 

 

 

 

230 VAC

No. 14

No. 12

No. 12

No. 8

 

 

 

 

 

 

 

Electric Motor Voltage Change Switch

1.ALWAYS make certain the electric motor's ON/OFF switch is in the "OFF" position and the power cord has been disconnected from the power source.

2.Remove the voltage change lock-out bolt and nut (Figure 6). Change the position of the voltage change toggle switch from 115 VAC to 230 VAC.The mixer is factory wired for 115 VAC operation.

3.Re-install the voltage change lock-out bolt and nut.

Figure 6. Voltage Change Switch

4.Important!, when changing the input voltage to the electric motor from 115 to 230 VAC, the plug on the electric motor power cord must also be changed. SeeTable 6 and Figure 7.

Table 6. Electric Motor Wiring Information

Motor

115-230 VAC - Single Phase

Horsepower

 

 

NEMA Plug Connector

Mating NEMA

Rating

 

Receptacle Connector

 

 

 

 

 

1.5 HP

L5-20P P/N EM940537

L5-20R P/N EM940538

(115 VAC)

 

 

 

 

 

1.5 HP

L6-20P P/N 940539

L6-20R P/N 940540

(230 VAC)

 

 

 

 

 

 

NEVER! disable or disconnect the

NOTE

ON/OFF switch on the electric motor.

It is provided for operator safety.Injury

 

 

may result if it is disable, disconnected

 

or improperly maintained.

PAGE 18 —MC-62P/S CONCRETE MIXERS — PARTS & OPERATION MANUAL — REV. #5 (09/13/04)

Page 18
Image 18
Multiquip MC-62S manual MC-62P/S CONCRETE MIXER - ELECTRIC MOTOR, Electric Motor Connection, Voltage Change Switch