08SLIM-LINE RC

10.0Technical Data Heating Performance Data

Power

 

 

 

 

Temperature Difference (°C)

 

 

 

Consumption

Fan Speed

 

Heat Output (watts)

 

 

Heat Output (Btu/h)

 

(watts)

 

20°

30°

40°

50°

60°

20°

30°

40°

50°

60°

 

Normal

860

1340

1820

2290

2770

2934

4572

6210

7813

9451

125

Medium

1130

1710

2280

2870

3460

3856

5835

7779

9792

11806

 

Boost

1470

2220

2960

3720

4460

5013

7575

10100

12693

15218

Tested in accordance with BS 4856 Part 1. Flow rate 340 ltr/h (75 gal/h).

Flow Rate Correction Factors:

455 ltr/h (100 gal/h) multiply by 1.03

227 ltr/h (50 gal/h) multiply by 0.96

113 ltr/h (25 gal/h) multiply by 0.85

Electrical supply 230V 50Hz Test pressure 20bar (1MPa)

Max working pressure 10bar (1MPa) Water connections 15mm compression Unit weight dry 14.3kg

Water capacity 0.51 litres

Approximate Hydraulic Resistance through Fan Convectors

Litres/h

mm wg

kPa

 

 

 

455

1771

17.4

340

1161

11.4

227

561

5.5

113

201

2.0

 

 

 

Noise levels in accordance with EN 23741

Fan

Sound Pressure at 2.5m (dBA)

Setting

 

Normal

21.9

Medium

30.6

Boost

39.7

Page 8
Image 8
Myson 1370064 manual Technical Data Heating Performance Data, Approximate Hydraulic Resistance through Fan Convectors