Panasonic 6367 manual

Models: 6367

1 2
Download 2 pages 558 b
Page 2
Image 2
6367

 

 

Type numbers

 

 

 

 

 

 

6367

Duct detector chamber (NOTE! Detector & base have to be ordered

 

 

 

separately).

 

6371-06

Venturi pipe 0.6 m (Incl. end plug.)

 

 

 

 

 

6371-15

Venturi pipe 1.5 m (Incl. end plug, plastic gasket and membrane gland TET

 

 

26-35.)

 

 

6371-28

Venturi pipe 2.8 m (Incl. end plug, plastic gasket and membrane gland TET

 

 

 

26-35.)

 

 

 

 

 

6372

Bracket

 

 

 

 

6373

Booster fan (ext. 24 V AC, 50 mA required)

 

 

 

 

6374

Filter

6367 can be mounted vertical or horizontal on the duct and 3 x the duct diameter before or 5 x the duct diameter after a disturbance (i.e. a bend, a filter or a damper.

Left: How to suit the pipe to different widths of the ventilation duct. Right: The Bracket 6372. Attached with each Duct detector chamber are detailed mounting and installation instructions.

 

Technical data

 

 

 

 

Duct air flow velocity (m/s)

0.2 to 15

 

 

 

 

Ambient temperature (°C)

 

 

operating

-10 to +50

storage

-25 to +75

 

 

 

Ambient humidity (% RH)

max. 95, non condensing

 

 

 

Ingress Protection rating

IP54

 

 

Size L x W x H (mm)

287 x 150 x 110 (the housing only)

 

 

 

 

Weight (g)

680 (the housing only)

 

 

 

Construction / Colour

ABS / Grey (RAL7035)

 

 

 

Compression glands

M16x1.5 for cable Ø=3-10 mm

 

 

Approvals

CE; EN 54

 

 

 

 

See also Product Leaflets / Technical data for the base and the detector to be used.

All technical features and data are subject to changes without notice, resulting from continuous development and improvement.

Product Leaflet

Date of issue

Revision / Date of revision

MEW00435

2004-02-05

2 / 2006-08-31

 

 

 