Panasonic 6367 manual Fire alarm systems Duct detector chamber, General, Venturi pipe

Models: 6367

1 2
Download 2 pages 558 b
Page 1
Image 1
Fire alarm systems

Fire alarm systems

Duct detector

chamber

6367

Only one pipe is required

Simple installation

For conventional as well as analog and addressable systems

General

The Uniguard Duct detector chamber 6367 is used when smoke is to be detected in a ventilation duct. Both the "venturi pipe" and the housing, where a smoke detector is to be placed, are especially designed for optimum airflow through the detector. The housing is made of grey ABS and the venturi pipe is made of aluminium. Supplied with two compression glands for cable entry.

6367 can be used in conventional as well as analog fire alarm systems, depending on the detector placed inside the housing.

The Photoelectric smoke detector 4352, plugged in the base 2324, is used in a conventional system (zone line input). An attached space ring (11 mm) is required between the base and the housing.

The Analog photoelectric smoke detector 4301, plugged in the analog base 3312, is used in an analog and addressable system. An attached space ring (19 mm) is required between the base and the housing.

Venturi pipe 6371

The venturi pipe is available in three lengths and can easily be shortened to suit the ventilation duct. An attached plug is to be placed in the end of the pipe.

A ventilation duct with a width < 0.6 m (diameter) requires a 0.6 m venturi pipe (6371-06), ended inside the duct.

A ventilation duct with a width > 0.6 m (diameter) requires an 1.5 or 2.8 m venturi pipe (6371-15 / -28), ended outside the duct.

See figure on the opposite page.

Air flow indicator

Abuilt-in air flow indicator gives a confirmation that the air from the ventilation duct is flowing through the venturi pipe and the detector. If not, a booster fan 6373 is available as an option.

Accessories

Bracket 6372, to be used when 6367 shall be mounted on a round ventilation duct. See figure on the opposite page.

Booster fan 6373, to be used when the air flow indicator is indicating no or very small air flow. The fan shall be mounted inside the housing and connected to the terminal block. External power supply (24 V AC, 50 mA) is required.

Filter 6374, can be used in an extremely dirty environment, as in a saw mill, a timber yard, etc. The filter shall be placed inside the housing, in a slot just before the detector.

Product applications

The Duct detector chamber can be used in the systems EBL500 / 512 / 128 / 1000 / 2000. It is intended for indoor use and in dry premises.

Panasonic Electric Works Fire & Security Technology Europe AB Citadellsvägen 23, SE-211 18 Malmö, Sweden

Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 info@mfstech.com • www.panasonic-fire-security.com

Page 1
Image 1
Panasonic 6367 manual Fire alarm systems Duct detector chamber, General, Venturi pipe, Air flow indicator, Accessories