(Revised 2010-11-15) page 6 of 30
5. Class I, Div 2 Installations require that power connections must be current limited at the power source
with an in-line fuse rated at 0.5A.
6. Class I, Div 2 installations require that all devices connected to this product must be UL listed for the
area in which it is installed.
7. Use 60/75ÂșC rated Copper wire, (022Nm) 2 inch-lbs Tightening torque for field installed connectors.
8. Limited Operating Voltage: 10-30V for Class I, Div 2 installations.
9. This apparatus is suitab le for use in Class I, Div 2, Groups A, B, C, and D, or unclassified or
nonhazardous locations only.
Package Contents
Please make sure the 102RAS Remote Access Server package contains the following items:
1. 102RAS Remote Access Server
2. Product CD
Contact your carrier if any items are damaged.
Installation
Read the following warning before beginning the installation:
WARNING
Never install or work on electrical equipment or cabling during periods of lightning activity. Never connect
or disconnect power when hazardous gasses are present.
Disconnect the power cable before removing any enclosure panel.
Do not operate the unit with any covers removed
Unpacking
Remove all the equipment from the packaging, and store the packaging in a safe place. File any damage
claims with the carrier.
Cleaning
Clean only with a damp cloth.