5
STOVE INSTALLATION
INSTALLING THE LEGS
To avoid being damaged during shipping, the stove has been bolted to the pallet and must be unbolted before the stove can be installed.
1.Remove the 4 nuts and washers from the underside of the pallet.
2.Lift the stove up and away from the pallet to clear the
threaded studs sticking through the pallet. Place the stove on its back onto a pro- tective surface such as a car- pet or blanket to avoid scratches during leg installa- tion.
STOVE INSTALLATION
If the stove is to be installed on a |
|
|
|
|
| ||||
combustible floor, it must be placed |
|
|
|
|
| ||||
on an approved |
|
|
|
|
| ||||
hearth pad, that extends 8" (200mm) |
|
|
|
|
| ||||
beyond the stove sides and back, |
|
|
|
|
| ||||
and 18" (455mm) to the front. It must |
|
|
|
|
| ||||
be installed with a minimum height |
|
|
|
|
| ||||
of 7’ between the stove base and |
|
|
|
|
| ||||
the ceiling. | FIGURE 4A | ||||||||
BACK WALL |
|
|
|
| BACK WALL |
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
B |
|
|
|
|
|
|
| ||
|
| 45° |
|
| WALLSIDE | ||||
|
|
| WALLSIDE |
|
| ||||
|
|
|
|
|
| ||||
| A |
| C |
|
| ||||
|
|
|
|
|
|
|
|
FIGURE 4B
SINGLE WALL CHIMNEY CONNECTOR*
|
| 1100/1100L/1150 | 1400/1400L | 1900 | |
| A | 12” (305 mm) | 12” (305 mm) | 22” (560 mm) | |
| B | 10” (254 mm) | 12” (305 mm) | 12” (305 mm) | |
| C | 6” (152 mm) | 6” (152 mm) | 8” (205 mm) | |
| * CLEARANCES CAN BE REDUCED WITH SHIELDING ACCEPTABLE TO LOCAL | ||||
| AUTHORITIES. REDUCED INSTALLATION MUST COMPY WITH NFPA 211 or | ||||
|
|
| |||
|
| DOUBLE WALL CHIMNEY CONNECTOR | |||
|
| 1100/1100L | 1400/1400L | 1900 | |
| A | 10” | (254 mm) | 10” (254 mm) | 22” (560 mm) |
| B | 6” | (152 mm) | 6” (152 mm) | 12” (305 mm) |
FIGURE 2B | C | 2” | (50 mm) | 4” (102 mm) | 8” (205 mm) |
|
|
|
|
|
3.Remove the four additional nuts from each of the four studs.
4.Use four of the nuts and washers removed above to install the legs as illustrated in FIGURES 2a & 2b.
5.Lift the stove up and gently set down on all four legs. Do not pivot unit up on its legs, as this could result in damage to the legs.
ALCOVE INSTALLATION
Model 1100 only may be installed, using a listed double wall connector, such as Security DL6 in Canada, the Simpson Duravent Plus DVL in the USA or an equivalent double wall connector, into an alcove having a depth of no more than 4 feet and a height of at least 7 feet. The mini- mum clearances are as shown in FIGURE 3.
9" |
| 6" |
|
14" | 4 FOOT | |
MAX. | ||
|
23"
ALCOVE
FIGURE 3
NOTE:CLEARANCES ARE UNABLE TO BE REDUCED FOR THE 1150 BY USING DOUBLE WALL PIPE.
CHIMNEY CONNECTION
A 6” diameter single wall stove pipe, used to connect the stove to the chimney, must be installed with the crimped end toward the stove. This will ensure that the moisture which condenses from the burning wood will flow back into the fire chamber. Each joint in the stove pipe must be se- cured with at least three sheet metal screws.
This room heater must be connected to:
1)A chimney complying with the requirements for Type HT chimneys in the Standard for Chimneys,
2)A
An insulated stainless steel chimney must be supported at the ceiling or roof and its installation must comply with its manufacturer's instructions.