FP-PWM-520 and cFP-PWM-520 14 ni.com
Mechanical DimensionsFigure5 shows the mechanical dimensions of the FP-PWM-520
installed on a terminal base. If you are using the cFP-PWM-520,
referto your Compact FieldPoint controller user manual for the
dimensions and cabling clearance requirements of the Compact
FieldPoint system.
Figure 5. FP-PWM-520 Mechanical Dimensions
Power RequirementsPower from network module............ 1 W
Isolation VoltageIsolation voltage is verified by a dielectric withstand test.
Channel-to-ground isolation
Continuous................................. 250 Vrms, Measurement
Category II
Dielectric withstand....................2,300 Vrms, 5 s max
Channel-to-channel isolation............None
EnvironmentalFieldPoint modules are intended for indoor use only. For outdoor
use, they must be mounted inside a sealed enclosure.
Operating temperature...................... –40 to 70 °C
Storage temperature.......................... –55 to 85 °C
Humidity........................................... 10 to 90% RH,
noncondensing
Maximum altitude.............................2,000 m
Pollution Degree............................... 2
109.5 mm
(4.31 in.)
91.44 mm
(3.60 in.)
107.19 mm
(4.22 in.)