Isolation Voltages
| |
Continuous ................................. | 600 Vrms, |
| Measurement Category II, |
| (Basic insulation) |
Withstand.................................... | 2,300 Vrms, verified by a 5 s |
| dielectric withstand test |
| |
Continuous ................................. | 300 Vrms, |
| Measurement Category II, |
| (Double insulation) |
Withstand.................................... | 2,300 Vrms, verified by a 5 s |
| dielectric withstand test |
Measurement Category II is for measurements performed on circuits directly connected to the electrical distribution system. This category refers to
Caution Do not connect the NI 9225E to signals or use for measurements within Measurement Categories III or IV.
© National Instruments Corp. | 19 NI 9225E Operating Instructions and Specifications |