12 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
7.5 Ton |
|
|
|
|
|
|
|
| OUTDOOR TEMPERATURE (DEG. F) |
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
| 0 |
|
| 10 |
|
| 20 |
|
| 30 |
|
| 40 |
|
|
| 50 |
|
| 60 |
|
| Suc. | Liquid | Disch. | Suc. | Liquid | Disch. | Suc. | Liquid | Disch. | Suc. | Liquid | Disch. | Suc. | Liquid | Disch. | Suc. | Liquid | Disch. | Suc. | Liquid | Disch. | ||
| Press |
| Press. | Temp. | Press. | Press. | Temp. | Press. | Press. | Temp. | Press. | Press. | Temp. | Press. | Press. | Temp. | Press. | Press. | Temp. | Press. | Press. | Temp. | |
| 19 |
| 134 | 135 | 20 | 140 | 135 | 21 | 146 | 136 | 22 | 152 | 136 | 32 | 162 |
| 157 | 51 | 199 | 198 | 61 | 248 | 179 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 20 |
| 141 | 133 | 21 | 146 | 133 | 22 | 151 | 134 | 23 | 156 | 134 | 33 | 169 |
| 154 | 52 | 206 | 193 | 62 | 255 | 185 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 21 |
| 148 | 131 | 22 | 152 | 131 | 23 | 156 | 132 | 24 | 160 | 132 | 34 | 176 |
| 151 | 53 | 213 | 189 | 63 | 262 | 191 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 22 |
| 155 | 129 | 23 | 158 | 129 | 24 | 160 | 130 | 25 | 163 | 130 | 35 | 183 |
| 148 | 54 | 220 | 184 | 64 | 269 | 198 |
| 23 |
| 162 | 127 | 24 | 163 | 127 | 25 | 165 | 128 | 26 | 167 | 128 | 36 | 190 |
| 146 | 55 | 227 | 180 | 65 | 276 | 204 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 24 |
| 169 | 125 | 25 | 169 | 125 | 26 | 170 | 126 | 27 | 171 | 126 | 37 | 197 |
| 143 | 56 | 234 | 175 | 66 | 283 | 210 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 25 |
| 176 | 123 | 26 | 175 | 123 | 27 | 175 | 124 | 28 | 174 | 124 | 38 | 204 |
| 140 | 57 | 241 | 171 | 67 | 290 | 216 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*Note: All pressures are listed in psig. and all temperatures in deg. F.
-Shaded Boxes indicate flooded conditions
-Rated Design Values. Suction Pressure will be lower than design value if indoor air flow, entering dry bulb, or entering wet bulb temperatures are lower than design.
-Discharge temperatures greater than charted values indicates a refrigerant undercharge.
REFRIGERANT CHARGING CHART Heating Mode of Operation
PROCEDURE FOR CHARGING 10-TON HEAT PUMP IN HEATING MODE.
1.Evacuate the refrigerant system.
2.Charge the system by weighing in 30 lbs
For line sets other than 15 feet add 9.0 oz.
3.Ensure that the unit is operating properly per the heating functional checkout in these installation instructions.