Nortec Industries NH Series installation manual 10-10, Page

Models: NH Series

1 42
Download 42 pages 13.66 Kb
Page 16
Image 16
Page 11 2008-10-01

FRONT VIEW

B

D

A

BACK VIEW

E

STEAM LINE CONNECTION 1.750inch OD

FILL WATER LINE, SINGLE OR DOUBLE, 1/2" NPT BY OTHERS

EXPLODED VIEW

TOP

BOTTOM VIEW

SECONDARY FILL LINE

RIGHT

 

 

ONLY FOR NHRS.

 

 

 

1/2" NPT BY OTHERS

LEFT

 

C

 

 

KNOCKOUT FOR

KNOCKOUT FOR

FRONT

OPTIONAL

POWER LINE AND

 

WATER INLET

HOLES FOR CONTROL

POWER KNOCKOUTS

 

WIRING

 

TO AND FROM

 

 

 

BREAKER

G

5"

(12.7cm)

F

ROOF PIPE

CHASES

FRONT

Manual background ROOF CURB

BY OTHERS

5"

(12.7cm)

 

Model

Weight (lbs)

 

0-50 lbs

99 lbs (45 kg)

 

50-100lbs137 lbs (62 kg)

 

100-200lbs206 lbs (93 kg)

 

 

Roof Curb Height

Model

Dimension F

Dimension G

Curb Height

** 0-50lbs

20.1" (51.1cm)

13.3" (33.8cm)

15"(38.1cm) Min.

50-100lbs

25.1" (63.8cm)

18.1" (46.0cm)

15"(38.1cm) Min.

100-200lbs

41.1" (104.4cm)

18.1" (46.0cm)

15"(38.1cm) Min.

4"

(10.16cm)

Model

Front

Minimum Required Clearance

3 3/4" MAX

Left

Right

Back(Curb Mount)

** 0-50lbs

24" (60.96cm)

0

20" (50.80cm)

6" (15.25cm)

(9.5cm)

50-100lbs

24" (60.96cm)

0

20" (50.80cm)

6" (15.25cm)

 

100-200lbs 38" (96.52cm)

0

20" (50.80cm)

6" (15.25cm)

 

 

 

Major Dimensions

 

Model

Dim. A

Dim. B

Dim. C

Dim. D

Dim. E

** 0-50lbs

34.7" (88.1cm)

25.0" (63.5cm)

15.5" (39.4cm)

3.4" (8.6cm)

7.9" (20.1cm)

50-100lbs

55.1" (140.0cm)

30.0" (76.2cm)

20.4" (51.8cm)

3.1" (7.8cm)

12.75" (32.4cm)

100-200lbs

55.1" (140.0cm)

46.0" (116.8cm)

20.4" (51.8cm)

3.1" (7.8cm)

12.75"/28.75" (32.4cm/73.1cm)

NHRS humidifiers under 50lbs/hour require a medium Outdoor Enclosure

NH Outdoor Enclosure Physical Data Sheet

Small/Medium/Large models

May 21 2008

Figure 1. Recommended Clearances and Curb Dimensions

10-10

Page 11 2008-10-01

Page 16
Image 16
Nortec Industries NH Series installation manual 10-10, Page